5 Description of the Functions 02.99 04.01 <strong>08</strong>.03<br />

5.6 Parameters for SIMODRIVE POSMO A<br />

P0097 / 61 Carry-out POWER-ON RESET<br />

300W 075W<br />

Min Standard Max Unit Data type Effective<br />

0 0 1 – I2 immed.<br />

A POWER-ON RESET for the drive can be carried-out using this parameter.<br />

0 Output status<br />

1 Carry-out POWER ON-RESET<br />

Note:<br />

After P0097 = 1, POWER ON-RESET is immediately carried-out. Communications is interrupted.<br />

The master does not receive an acknowledgment.<br />

Available with software version 1.5 and higher.<br />

P0098 / 62<br />

300W 075W<br />

Reset reference point set<br />

Min Standard Max Unit Data type Effective<br />

0 0 1 – I2 immed.<br />

0 No reference point set<br />

1<br />

Note:<br />

Reference point set<br />

For a stationary, referenced axis, when writing zero into P98 = 0, the ”No reference point set”<br />

status is re-established.<br />

Refer to ZSW.11<br />

Available from SW 1.4.<br />

P0099:21 / 63 Program management<br />

300W 075W<br />

Min Standard Max Unit Data type Effective<br />

0 0 27 – I2 immed.<br />

The parameter specifies the start of a program.<br />

P99:0 ––> no significance<br />

P99:1 ––> start, program 1 (standard value = 13)<br />

P99:2 ––> start, program 2 (standard value = 18)<br />

P99:3 ––> start, program 3 (standard value = 23), etc.<br />

Note:<br />

The parameter value can be changed while traversing.<br />

P0100 / 64<br />

300W 075W<br />

Control word simulation<br />

Min Standard Max Unit Data type Effective<br />

0 0 FFFF – V2 immed.<br />

If the cyclic communication with Master Class 1 is interrupted for more than 3 seconds, this<br />

control word is used. All terminal signals remain active with priority.<br />

= 0 ––> no simulation<br />

= 17471 dec (= 443F hex)<br />

Note:<br />

––> value recommended for simulation<br />

The parameter value can be changed while traversing.<br />

P101 must be > 0.<br />

When operating the system with Master Class 2 alone (SimoCom A), the simulation mode is<br />

activated immediately when making entries in P100.<br />

Available from SW 1.2.<br />

5-204<br />

Siemens AG <strong>2003</strong> All rights reserved<br />

SIMODRIVE POSMO A <strong>User</strong> <strong>Manual</strong> (POS1) – <strong>08</strong>.03 <strong>Edition</strong>