SIMODRIVE POSMO A <strong>User</strong> <strong>Manual</strong> (POS1) – <strong>08</strong>.03 <strong>Edition</strong><br />

5.6 Parameters for SIMODRIVE POSMO A<br />

P0101:11 / 65 Block sequence in standalone operation<br />

5 Description of the Functions<br />

300W 075W<br />

Min Standard Max Unit Data type Effective<br />

0 0 27 – I2 immed.<br />

For standalone operation, a maximum of 10 traversing blocks can be entered in the range 3 to<br />

27 in P101:11.<br />

These specified blocks are executed one after the other in the standalone mode.<br />

P101:0 ––> no significance<br />

P101:1 ––> 1st block<br />

P101:2 ––> 2nd block, etc.<br />

Note:<br />

The parameter value can be changed while traversing.<br />

Available from SW 1.2.<br />

P0700 / 2BC Operating mode selector switch<br />

300W 075W<br />

Min Standard Max Unit Data type Effective<br />

1 2 2 – I2 PO<br />

This parameter is used for selecting the operating mode.<br />

Operating mode changes only take effect when the parameter set is saved in the FEPROM<br />

(P971 0 ––> 1) followed by a Power-On Reset (P097 0 ––> 1).<br />

If SimoCom A is in use, the operating mode should be selected via the configuration dialog.<br />

The following operating modes are supported:<br />

1 ––> Speed setpoint<br />

2 ––> Positioning<br />

The parameter corresponds to parameter 930.<br />

Note:<br />

Before changing the operating mode load factory default setting via P970.<br />

This allows achieving a pre-defined initial status.<br />

Available with software version 2.0 and higher.<br />

P<strong>08</strong>80 / 370<br />

300W 075W<br />

N-SETPOINT normalization<br />

Min Standard Max Unit Data type Effective<br />

–100000 4096 100000 rpm C4 immed.<br />

This parameter defines the normalization as to which speed sets in at the gear output when a<br />

setpoint of 1000h (4096d) is specified via the control word (STW).<br />

P0918 / 396<br />

300W 075W<br />

PROFIBUS node address<br />

Min Standard Max Unit Data type Effective<br />

– – – – I2 RO<br />

The node address is read from address switch S1.<br />

P0928 / 3A0<br />

300W 075W<br />

Control authority PZD<br />

Min Standard Max Unit Data type Effective<br />

1 1 2 – V2 immed.<br />

Request for control authority from a Class 2 DP master.<br />

Note:<br />

Available from SW 1.4.<br />

5-205<br />

5