5.6 Parameters for SIMODRIVE POSMO A<br />
P0101:11 / 65 Block sequence in standalone operation<br />
5 Description of the Functions<br />
300W 075W<br />
Min Standard Max Unit Data type Effective<br />
0 0 27 – I2 immed.<br />
For standalone operation, a maximum of 10 traversing blocks can be entered in the range 3 to<br />
27 in P101:11.<br />
These specified blocks are executed one after the other in the standalone mode.<br />
P101:0 ––> no significance<br />
P101:1 ––> 1st block<br />
P101:2 ––> 2nd block, etc.<br />
Note:<br />
The parameter value can be changed while traversing.<br />
Available from SW 1.2.<br />
P0700 / 2BC Operating mode selector switch<br />
300W 075W<br />
Min Standard Max Unit Data type Effective<br />
1 2 2 – I2 PO<br />
This parameter is used for selecting the operating mode.<br />
Operating mode changes only take effect when the parameter set is saved in the FEPROM<br />
(P971 0 ––> 1) followed by a Power-On Reset (P097 0 ––> 1).<br />
If SimoCom A is in use, the operating mode should be selected via the configuration dialog.<br />
The following operating modes are supported:<br />
1 ––> Speed setpoint<br />
2 ––> Positioning<br />
The parameter corresponds to parameter 930.<br />
Note:<br />
Before changing the operating mode load factory default setting via P970.<br />
This allows achieving a pre-defined initial status.<br />
Available with software version 2.0 and higher.<br />
P<strong>08</strong>80 / 370<br />
300W 075W<br />
N-SETPOINT normalization<br />
Min Standard Max Unit Data type Effective<br />
–100000 4096 100000 rpm C4 immed.<br />
This parameter defines the normalization as to which speed sets in at the gear output when a<br />
setpoint of 1000h (4096d) is specified via the control word (STW).<br />
P0918 / 396<br />
300W 075W<br />
PROFIBUS node address<br />
Min Standard Max Unit Data type Effective<br />
– – – – I2 RO<br />
The node address is read from address switch S1.<br />
P0928 / 3A0<br />
300W 075W<br />
Control authority PZD<br />
Min Standard Max Unit Data type Effective<br />
1 1 2 – V2 immed.<br />
Request for control authority from a Class 2 DP master.<br />
Note:<br />
Available from SW 1.4.<br />
5-205<br />
5