P0056 / 38 Operating options<br />

Siemens AG <strong>2003</strong> All rights reserved<br />

SIMODRIVE POSMO A <strong>User</strong> <strong>Manual</strong> (POS1) – <strong>08</strong>.03 <strong>Edition</strong><br />

5 Description of the Functions<br />

5.6 Parameters for SIMODRIVE POSMO A<br />

300W 075W<br />

Min Standard Max Unit Data type Effective<br />

0 0 FFFF Hex V2 immed.<br />

Bit 1.0 Drive referenced and behavior after restart (from SW 1.2)<br />

= 00: The motor is referenced when powering-up again, if it was already referenced<br />

when powered-down and is stationary. The behavior is the same as before<br />

SW 1.2.<br />

= 01: The motor is referenced when powering-up again if it was already referenced<br />

when powered-down and was not stationary (ZSW.13).<br />

= 1x: The motor is not referenced when powering-up again.<br />

(x: the bit can either 0 or 1)<br />

Bit 2<br />

The following applies from SW 2.0:<br />

The drive is always dereferenced in the ”Speed setpoint” operating mode (P930).<br />

Bit 0 and bit 1 have no function in this operating mode.<br />

P gain at standstill (from SW 1.3)<br />

= 0: Holding controller P gain active (P57)<br />

= 1: Speed controller P gain active (P54)<br />

Bit 3<br />

The following applies from SW 2.0:<br />

The speed controller is always active in the ”Speed setpoint” operating mode (P930).<br />

Bit 2 has no meaning here.<br />

P54 is effective at zero speed.<br />

Response of Bit 10 in the status word ”Setpoint position reached” (as of SW 1.6)<br />

= 0: ”Setpoint position reached” is signalled when:<br />

– traversing block fully completed<br />

– Abort of the traversing block by: Fault, Stop or OFF commands<br />

= 1: ”Setp. pos. reached” is signalled only after full completion of the traversing block.<br />

Bit 4 Open holding brake (from SW 1.4)<br />

= 0: Brake sequence control effective<br />

= 1: Open holding brake<br />

Bit 5 Monitoring, holding brake undervoltage (from SW 1.4)<br />

= 0: De-activated (P947.12)<br />

= 1: Activated (P947.12)<br />

Bit 6 Open holding brake is also effective for external holding brakes (from SW 1.4)<br />

= 0: Brake sequence control effective<br />

= 1: Open holding brake is also effective for an external holding brake<br />

P0057 / 39<br />

300W<br />

P gain, holding controller standstill<br />

Min Standard Max Unit Data type Effective<br />

5 20 250 – I4 immed.<br />

P gain for axis standstill.<br />

Note:<br />

Refer to P56.2<br />

075W<br />

Min Standard Max Unit Data type Effective<br />

50 100 250 – I4 immed.<br />

P gain for axis standstill.<br />

Note:<br />

Refer to P56.2<br />

Available from SW 1.3.<br />

5-199<br />