714 / P947.14 Error in the FEPROM<br />

Siemens AG <strong>2003</strong> All rights reserved<br />

SIMODRIVE POSMO A <strong>User</strong> <strong>Manual</strong> (POS1) – <strong>08</strong>.03 <strong>Edition</strong><br />

6.2 Faults and warnings<br />

Cause We have detected a fault in the non-volatile memory (FEPROM).<br />

Remedy Additional information? ––> Evaluate P954<br />

Acknowledgement Remove cause, set STW.7 = 1/0 and STW.0 = 0/1<br />

Stop response Pulse suppression<br />

715 / P947.15 System error<br />

Cause An internal fault was detected in the drive.<br />

Remedy Activate/deactivate positioning motor.<br />

Check and correct the motor data.<br />

Posmo A 75W: Replace the positioning motor.<br />

Posmo A 300W: Replace the drive unit.<br />

Acknowledgement Remove cause, set STW.7 = 1/0 and STW.0 = 0/1<br />

Stop response Pulse suppression<br />

800 / P953.0 Electronics temperature warning<br />

6 Fault Handling and Diagnostics<br />

Cause The electronics temperature is > 90 degrees Celsius.<br />

If the permissible maximum electronics temperature is exceeded for<br />

longer than the time specified in P29 (electronics temperature tolerance<br />

time), then a fault is output and the drive is powered-down.<br />

The ambient temperature is too high.<br />

Remedy Observe the de-rating characteristic.<br />

Reduce ambient temperature.<br />

Acknowledgement not required<br />

Stop response None<br />

801 / P953.1 Motor i2t monitoring<br />

Cause The I2t limiting for the motor current is active, the current is limited to<br />

Irated.<br />

The load or the load duty cycle is too high.<br />

Remedy Reduce load duty cycle.<br />

Acknowledgement not required<br />

Stop response None<br />

802 / P953.2 Standstill monitoring<br />

Cause The motor was moved out of the standstill area (P14) in the closed-loop<br />

controlled status.<br />

Note:<br />

The warning is only signaled if the appropriate fault is suppressed.<br />

Remedy –<br />

Acknowledgement not required<br />

Stop response None<br />

6-221<br />