WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 CHAPTER 4<br />

Table 4.1-1 Design Classes <strong>of</strong> Structures, Systems, and Components at the WIPP Facility Page 2 <strong>of</strong> 5<br />

System/Component<br />

Design<br />

Class<br />

(Note 1)<br />

Seismic/Tornado Design<br />

Requirements<br />

Design Class Function<br />

PLANT MONITORING AND COMMUNICATION SYSTEM (SDD-CMOO)<br />

Central Monitoring System IIIA Monitors important facility parameters<br />

ENVIRONMENTAL MONITORING SYSTEM (SDD-EM00)<br />

Volatile Organic Compound (VOC) Monitoring Equipment<br />

and sub-systems<br />

IIIA<br />

Monitors release <strong>of</strong> VOCs<br />

HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEM (SDD-HV00)<br />

Exhaust Filtration System II Design Class Interface. (Control <strong>of</strong> radioactive<br />

effluent)<br />

HEPA Filters II Control <strong>of</strong> radioactive effluent<br />

Tornado Dampers II DBE, DBT Control <strong>of</strong> radioactive effluent<br />

Exhaust Systems HV02, (Bldg 411, RH HVAC), and HV04<br />

(Station A and Bldg 413, Exhaust Filter Building HVAC)<br />

IIIA<br />

Design Class Interface. (Provide filtration and<br />

maintain differential pressure)<br />

HVAC for the CMR IIIA Design Class Interface. (Maintains acceptable CMR<br />

environment)<br />

RADIATION MONITORING SYSTEM (SDD-RM00)<br />

Stations A3, B2, C, and D1 (including the UPSs) II DBE, DBT Monitors radioactive effluents<br />

The remainder <strong>of</strong> the RMS SSCs are Design Class IIIA<br />

(except PV00 equipment which is IIIB)<br />

UNDERGROUND HOIST SYSTEM (SDD-UH00)<br />

IIIA<br />

Monitors radioactive effluents<br />

<strong>Waste</strong> Hoist and Equipment IIIA (Note 3) Failure could cause radioactive material release<br />