WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 2- 10-160B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions Total Rank<br />

(Cons., Freq)<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

10. Unload Carriage Units in Hot Cell<br />

10A-1 Puncture drum<br />

in the Hot Cell<br />

with PAR®<br />

manipulator<br />

Human error;<br />

Equipment<br />

failure<br />

Potential for<br />

breach <strong>of</strong> drum;<br />

Potential for<br />

spread <strong>of</strong><br />

contamination;<br />

Potential for<br />

<strong>of</strong>fsite and onsite<br />

consequences;<br />

Potential for<br />

release <strong>of</strong><br />

hazardous waste;<br />

Potential for<br />

operational down<br />

time.<br />

Training and Procedures;<br />

Facility design;<br />

Ventilation systems;<br />

CAMs; Emergency Response<br />

Procedure;<br />

Preventive Maintenance<br />

Program on PAR®<br />

manipulator equipment and<br />

controls; Crane design;<br />

Inspection <strong>of</strong> shield door<br />

closed in the CUR; Shield plug<br />

in Hot Cell is in place Shield<br />

door crane interlocks mitigate<br />

direct radiation exposure<br />

and/or spread <strong>of</strong><br />

contamination.<br />

NAI 4,4 Facility Worker -<br />

1,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

Radiological<br />

Hazard Only<br />

10B-1 While lifting<br />

the drum, drum<br />

lid comes <strong>of</strong>f in<br />

the Hot Cell<br />

Human error;<br />

Equipment<br />

failure; Drum lid<br />

failure<br />

Potential for drum<br />

breach (1 drum);<br />

Potential for<br />

spread <strong>of</strong><br />

contamination;<br />

Potential for loss<br />

<strong>of</strong> production;<br />

Potential for<br />

onsite and <strong>of</strong>fsite<br />

consequences.<br />

Training and procedure;<br />

Preventive Maintenance<br />

Program on crane;<br />

Drum design;<br />

Drum inspection;<br />

WAC;<br />

Ventilation;<br />

Shield door closed in the CUR;<br />

Shield plug in Hot Cell is in<br />

place.<br />

NAI 3,4 Facility Worker -<br />

1,4<br />

Onsite Worker - 3,4<br />

Offsite - 3,4<br />

C-50