WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 2- 10-160B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions Total Rank<br />

(Cons., Freq)<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

4D-1 Cask falls <strong>of</strong>f<br />

<strong>of</strong> RCTC in RH<br />

Bay while lid is<br />

loose<br />

Derailment;<br />

Vehicle impact;<br />

Shield door<br />

impact<br />

Potential for loss<br />

<strong>of</strong> production (CH<br />

and RH);<br />

Potential for<br />

breach <strong>of</strong> drums;<br />

Potential for direct<br />

radiological<br />

exposure to<br />

facility worker;<br />

Potential for onsite<br />

consequence;<br />

Potential for <strong>of</strong>fsite<br />

consequence;<br />

Potential for<br />

spread <strong>of</strong><br />

contamination;<br />

Release <strong>of</strong><br />

hazardous<br />

material;<br />

Potential for<br />

facility and<br />

equipment<br />

damage<br />

Design <strong>of</strong> transfer car, shield<br />

doors, cask, rails;<br />

Emergency Response<br />

Procedure;<br />

Limited speed on transfer car;<br />

DOT Type A Drums;<br />

Ventilation system;<br />

Training and Procedures;<br />

Nuclear coating on floor;<br />

ARMs and CAMs.<br />

A-5) Calculation<br />

note needed to<br />

verify validity <strong>of</strong><br />

RCTC derailment.<br />

4,4 Facility Worker -<br />

4,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

4E-1 Pinch points<br />

while closing<br />

Cask<br />

Unloading<br />

Room Shield<br />

Door<br />

Potential for<br />

personnel injury<br />

NAI 1,4 NA Industrial<br />

Hazard Only<br />

C-39