WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 2- 10-160B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions Total Rank<br />

(Cons., Freq)<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

19. Storage Mode (covered by <strong>DOE</strong>/WIPP-00-2305)<br />

20. Natural Events<br />

20-1<br />

Loss <strong>of</strong><br />

confinement in<br />

RH Bay due to<br />

seismic event<br />

(lid is loose on<br />

cask)<br />

Seismic event<br />

Potential for<br />

major disruption<br />

<strong>of</strong> facility<br />

operations;<br />

Potential damage<br />

to cask and/or<br />

canister; Potential<br />

breach <strong>of</strong> drums<br />

due to loose cask<br />

lid in RH Bay;<br />

Potential for loss<br />

<strong>of</strong> site utilities;<br />

Potential to<br />

release radioactive<br />

material; Potential<br />

for fire; Potential<br />

for explosion;<br />

Potential for<br />

worker injury or<br />

fatality; Potential<br />

for breach <strong>of</strong><br />

drums; Potential<br />

for onsite/<strong>of</strong>fsite<br />

consequences;<br />

Potential for<br />

facility worker<br />

exposure.<br />

<strong>Waste</strong> Handling Building is<br />

DBE qualified;<br />

Crane is DBE qualified;<br />

Emergency Response Plan;<br />

Recovery Plan; 10-160B Cask<br />

design - meets DOT Type B<br />

shipping container certification<br />

requirements;<br />

HVAC system shutdown<br />

switch; Hot Cell is DBE<br />

qualified.<br />

A-12) Verify the<br />

Mezzanine design<br />

is DBE qualified.<br />

4,3 Facility Worker -<br />

4,3<br />

Onsite Worker - 4,3<br />

Offsite - 4,3<br />

Worker injury or<br />

fatality could<br />

occur as the<br />

result <strong>of</strong> the<br />

earthquake<br />

alone.<br />

Radiological<br />

impact would<br />

likely be<br />

extensive.<br />

20-2 Full facility fire Seismic Potential for<br />

breach <strong>of</strong> drums;<br />

Potential for<br />

onsite/<strong>of</strong>fsite<br />

consequences;<br />

Potential for<br />

facility worker<br />

exposure.<br />

<strong>Waste</strong> Handling Building DBE<br />

qualified;<br />

Crane is DBE qualified;<br />

PAR® is DBE qualified;<br />

Hot Cell is DBE qualified.<br />

NAI 4,3 Facility Worker -<br />

4,3<br />

Onsite Worker - 4,3<br />

Offsite - 4,3<br />

C-58