WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 1- 72B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions or<br />

Recommendations<br />

Total Rank<br />

(Cons.,Freq )<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

7 - 10 Hydraulic fluid<br />

fire<br />

Leak <strong>of</strong><br />

hydraulic fluid<br />

from facility<br />

cask rotating<br />

device;<br />

Unknown<br />

Ignition Source<br />

Potential for<br />

damage to facility<br />

cask and other<br />

equipment (air<br />

hose, power<br />

cables);<br />

Potential adverse<br />

impact to<br />

ventilation<br />

system;<br />

Potential for<br />

generation <strong>of</strong><br />

toxic fumes;<br />

Potential worker<br />

injury from smoke<br />

inhalation<br />

Limited quantity<br />

(approximately 40 gallons) <strong>of</strong><br />

hydraulic fluid;<br />

Smoke alarms;<br />

Sprinkler system;<br />

Evacuation plan for Facility<br />

Cask loading room;<br />

Emergency exit from Facility<br />

Cask loading room;<br />

Sump in room<br />

R-14 Add<br />

combustible<br />

loading limits for<br />

waste handling<br />

building to FHA<br />

4,4 Facility Worker -<br />

4,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

Facility worker<br />

injury could<br />

result from<br />

smoke inhalation<br />

(industrial<br />

accident).<br />

Minimal<br />

potential for<br />

radiological<br />

impact.<br />

7 - 11 Incorrect<br />

sequence -<br />

Cask is rotated<br />

to horizontal<br />

position before<br />

shield valves<br />

are closed with<br />

grapple still<br />

attached<br />

Control Loop<br />

Failure<br />

Potential for direct<br />

radiological<br />

exposure to<br />

personnel<br />

Interlocked to grapple hoist<br />

position;<br />

Grapple design will not<br />

release;<br />

Physical restraints to keep<br />

canister in place;<br />

Pre-operational checks for<br />

control system;<br />

Preventive Maintenance<br />

Program for control system;<br />

Shielding for operator at<br />

control panel<br />

R-15 Verify<br />

rotating equipment<br />

design will<br />

preclude<br />

radiological<br />

exposure as a result<br />

<strong>of</strong> this event.<br />

1,4 Facility Worker -<br />

1,4<br />

Onsite Worker - 1,4<br />

Offsite -NA<br />

Radiological<br />

hazard only.<br />

Minimal impact<br />

to facility and<br />

workers<br />

7 - 12 Excessive<br />

movement -<br />

Facility cask<br />

rotates freely<br />

during rotation<br />

to horizontal<br />

position<br />

Human Error;<br />

Mechanical<br />

Failure<br />

Potential<br />

equipment<br />

damage<br />

Pre-operational checks for<br />

rotation equipment function;<br />

Mechanical design <strong>of</strong> facility<br />

cask transfer car prevents<br />

over-rotation;<br />

NAI NA NA No release <strong>of</strong><br />

radioactive<br />

material<br />

C-15 January 23, 2003