WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 2- 10-160B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions Total Rank<br />

(Cons., Freq)<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

7. Reinstall the Cask on the Trailer in RH Bay<br />

7AEFGHIJK<br />

L-1<br />

Pinch points<br />

while<br />

reinstalling the<br />

cask on the<br />

trailer<br />

Potential for<br />

personnel injury<br />

NAI 1,4 NA Industrial<br />

Hazard Only<br />

7BCD-1<br />

Cask dropped<br />

while lifting<br />

from the RCTC<br />

in RH Bay<br />

Same as event<br />

3H-1<br />

Industrial<br />

Hazard Only<br />

Cask does not<br />

contain TRU<br />

waste drums.<br />

8. Reinstall the Upper Impact Limiter in RH Bay<br />

8ABCDE-1<br />

Pinch points<br />

while<br />

reinstalling the<br />

upper impact<br />

limiter on the<br />

cask<br />

Potential for<br />

personnel injury<br />

NAI 1,4 NA Industrial<br />

Hazard Only<br />

9. Move Empty WIPP Canister into Hot Cell and Prepare WIPP Canister<br />

9-1 Fire in Hot Cell<br />

while<br />

containing<br />

stored waste<br />

Electrical short<br />

Potential for<br />

equipment<br />

damage;<br />

Potential to shut<br />

down operations;<br />

Potential for drum<br />

breach; Potential<br />

for onsite and<br />

<strong>of</strong>fsite<br />

consequences;<br />

Damage to Hot<br />

Cell.<br />

Fire Loading/ Combustible<br />

Control Program;<br />

Preventive Maintenance<br />

Program on electrical<br />

equipment in the immediate<br />

area; Hot Cell design;<br />

Combustible loading<br />

inspections; Procedures &<br />

Training; Limited ignition<br />

sources<br />

R-3) Verify FHA<br />

covers Hot Cell<br />

4,4 Facility Worker -<br />

4,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

Radiological<br />

Hazard Only<br />