WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 1- 72B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions or<br />

Recommendations<br />

Total Rank<br />

(Cons.,Freq )<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

10 - Canister emplacement in borehole<br />

10-1 Loss <strong>of</strong> control<br />

- Forklift drops<br />

Facility cask<br />

onto<br />

emplacement<br />

equipment<br />

Human Error;<br />

Equipment<br />

Failure<br />

Potential for<br />

damage to<br />

emplacement<br />

equipment;<br />

Breach <strong>of</strong> the<br />

waste cannister,<br />

Personnel<br />

Exposure,<br />

Release to the<br />

environment,<br />

Potential for<br />

processing delays<br />

Equipment design NAI 4,4 Facility Worker -<br />

4,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

10-2 Hydraulic<br />

fluid/diesel fuel<br />

fire<br />

Hydraulic fluid<br />

or diesel fuel<br />

leak;<br />

Unknown<br />

Ignition Source<br />

Potential for<br />

radiological<br />

exposure to<br />

personnel;<br />

Potential for<br />

damage to facility<br />

cask and canister;<br />

Potential for<br />

canister breach;<br />

Potential worker<br />

injury or fatality<br />

Vented canister;<br />

Fire suppression system (on<br />

forklift);<br />

Underground ventilation<br />

system;<br />

Rescue program;<br />

Mine worker training;<br />

Mine evacuation plan<br />

A-7 Same Action<br />

as for 9-7. Verify<br />

that the fire<br />

response plan<br />

addresses this event<br />

R-16 Same<br />

recommendation<br />

as for 9-7.<br />

Investigate the<br />

potential for<br />

hydrogen<br />

generation<br />

(through radiolysis)<br />

in vicinity <strong>of</strong><br />

emplacement<br />

activities<br />

4,4 Facility Worker -<br />

4,4<br />

Onsite Worker - 4,4<br />

Offsite - 4,4<br />

Worker fatality<br />

could occur as<br />

the result <strong>of</strong> the<br />

fire (industrial<br />

safety issue).<br />

Radiological<br />

impact could be<br />

considerable due<br />

to facility cask<br />

not being<br />

qualified for fire<br />

C-21 January 23, 2003