WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 2- 10-160B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions Total Rank<br />

(Cons., Freq)<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

9-6 External fire to<br />

Hot Cell<br />

Hydraulic fuel<br />

fire;<br />

Fire in the crane<br />

maintenance<br />

room; Electrical<br />

fire<br />

Potential to form<br />

toxic gas from<br />

neoprene;<br />

Industrial hazards<br />

from a fire.<br />

Fire brigade - fire protection;<br />

Fire Loading/ Combustible<br />

Control Program;<br />

Training and procedures;<br />

Fire detection in Operation<br />

Gallery (outside <strong>of</strong> Hot Cell);<br />

Sprinkler system;<br />

Hot Cell design;<br />

Ventilation.<br />

A-6) Verify gallery<br />

combustible<br />

loading with<br />

facility FPE.<br />

2,4 NA Industrial<br />

Hazard Only<br />

Concrete<br />

structure<br />

prevents fire<br />

from spreading<br />

to Hot Cell<br />

9-7 Criticality in<br />

the Hot Cell<br />

NA NA NA A-7) Need to<br />

update criticality<br />

analysis to address<br />

this deviation.<br />

NA NA HAZOP did not<br />

address<br />

criticality, but<br />

will be<br />

addressed in<br />

separate<br />

evaluation.<br />

9-8 Mishandling <strong>of</strong><br />

HEPA Filter<br />

Human error<br />

Potential for<br />

facility worker<br />

exposure<br />

Training and procedures for<br />

filter change-out; Personal<br />

Protective Equipment; Bag-out<br />

process for HEPA filter<br />

change-out<br />

NAI 2,4 Facility Worker -<br />

2,4<br />

Onsite Worker -<br />

NA<br />

Covered as part<br />

<strong>of</strong> Maintenance<br />

Program<br />

Offsite - NA<br />

9-9 High Radiation<br />

- Direct<br />

radiological<br />

exposure<br />

Human error;<br />

Worker<br />

inadvertently<br />

enters an area<br />

where waste<br />

handling is<br />

happening.<br />

(Transfer Cell or<br />

Hot Cell)<br />

Potential for<br />

facility worker<br />

exposure<br />

Training and procedures;<br />

Administrative controls for<br />

lock and key;<br />

ARM indicators in the Hot<br />

Cell and Transfer Cell;<br />

.<br />

NAI 3,4 Facility Worker -<br />

3,4<br />

Onsite Worker -<br />

NA<br />

Offsite - NA<br />

Radiological<br />

Hazard Only<br />

C-46