WIPP RH PSAR <strong>DOE</strong>/WIPP-03-3174 APPENDIX C<br />

Table 1- 72B HAZOP Table<br />

Study Node<br />

Event No.<br />

Deviation Causes Consequences Existing Safeguards Actions or<br />

Recommendations<br />

Total Rank<br />

(Cons.,Freq )<br />

Radiological Rank<br />

(Cons.,Freq)<br />

Comments<br />

3 - 4 Crane drops<br />

outer lid onto<br />

cask<br />

Human Error;<br />

Equipment<br />

Failure - Crane<br />

Potential damage<br />

to cask;<br />

Potential damage<br />

to inner container<br />

(ICV) lid;<br />

Potential damage<br />

to outer lid sealing<br />

surface;<br />

Potential for<br />

severe worker<br />

injury<br />

Cask design;<br />

Crane operator training;<br />

<strong>Waste</strong> handling procedures;<br />

Cask (ICV lid) design;<br />

Lifting fixture design<br />

NAI 3,4 NA Industrial hazard<br />

only<br />

4 - Cask transfer to unloading room<br />

4 - 1 Over-speed -<br />

Impact<br />

involving<br />

transfer car<br />

with road cask<br />

-<br />

transfer car<br />

stays on rails<br />

Human Error;<br />

Equipment<br />

Failure;<br />

foreign object on<br />

rails<br />

Potential<br />

production<br />

downtime;<br />

Potential for<br />

damage to<br />

equipment;<br />

Potential for<br />

severe worker<br />

injury<br />

Transfer car design;<br />

Rail design;<br />

Cask design;<br />

Operator training;<br />

<strong>Waste</strong> handling procedures;<br />

Limited transfer car speed<br />

NAI 3,4 NA Industrial hazard<br />

only<br />

4 - 2 Road cask<br />

transfer car<br />

derails and falls<br />

over<br />

Human Error -<br />

Failure to<br />

replace<br />

removable rails<br />

at cask<br />

unloading room<br />

entry;<br />

Foreign object<br />

on rails<br />

Potential for<br />

production<br />

downtime;<br />

Potential for<br />

worker injury or<br />

fatality<br />

Road Cask transfer car design;<br />

Cask/canister design;<br />

Operator training;<br />

<strong>Waste</strong> handling procedures;<br />

NAI 4,4 NA Worker injury or<br />

fatality could<br />

result from the<br />

industrial<br />

accident.<br />

C-8 January 23, 2003