Safeguard Catalogue Infrastucture Remarks<br />

____________________________________________________________________ .........................................<br />

S 1.9 Fire sealing of trays<br />

Initiation responsibility: Head of <strong>Site</strong>/Bldg Technical Service; site fire<br />

protection officer<br />

Implementation responsibility: <strong>Site</strong>/Bldg Technical Service; site fire<br />

protection officer<br />

In buildings with several fire cuts, it can hardly be avoided that trays will lead<br />

through fire walls and ceilings. After installation of lines, the breaches must be<br />

shielded in keeping with the fire-resistance value of the wall/ceiling. In order<br />

to provide for retrofitting, appropriate material (e.g. fire-resistant padding)<br />

should be used. <strong>The</strong> relevant VdS guidelines should be complied with.<br />

Negative approach example:<br />

In a multi-storey office building in Bonn, several networks were run through a<br />

common rising line from the basement to the uppermost storey. All ceiling<br />

breaches had been made with ample reserves, but had, after wiring and pipe<br />

installation, not been closed. In the basement, large quantities of paper and<br />

cloth were stored in the vicinity of the front end of the line. <strong>The</strong> rising line beginning<br />

immediately above would, in case of fire, have had the effect of a fireplace<br />

(chimney). Smoke and fire would have spread to all floors in no time.<br />

Additional controls:<br />

- Has the person responsible for fire protection been consulted with regard to<br />

route planning?<br />

- Have possible alternatives been explored as regards line routing?<br />