Proceedings <strong>of</strong> the National Conference on<br />

Trends and Advances in Mechanical Engineering,<br />

<strong>YMCA</strong> <strong>University</strong> <strong>of</strong> <strong>Science</strong> & <strong>Technology</strong>, Faridabad, Haryana, Oct <strong>19</strong>-<strong>20</strong>, <strong>20</strong>12<br />

Property data for different component <strong>of</strong> GSHP (R22)<br />

S. no. Description Fluid Temp T<br />

(c)<br />

Pressure<br />

P(bar)<br />

Specific<br />

Enthalpy<br />

Specific<br />

Entropy<br />

0 _______ Refrigerant 10 1.0132 4<strong>19</strong>.8 1.949<br />

0` ________ Water 10 1.0132 42.18 0.151<br />

0`` _________ Brine water 10 1.0132 42.18 0.151<br />

1 Compressor<br />

inlet<br />

2 Compressor<br />

outlet<br />

3 Condenser<br />

outlet<br />

4 Evaporator<br />

inlet<br />

5 Fan coil<br />

Inlet<br />

6 Fan coil Out<br />

Let<br />

Refrigerant -6 3.141 404.6 1.782<br />

refrigerant 99.2 <strong>19</strong>.11 464.7 1.823<br />

refrigrant 40.8 <strong>19</strong>.11 464.7 1.172<br />

refrigrant -10.99 3.14 251.45 1.<strong>19</strong>8<br />

water 45 2.50 188.64 0.6381<br />

water 39.9 2.50 167.34 0.5707<br />

7<br />

8<br />

GHE water<br />

Pump inlet<br />

GHE water<br />

Pump outlet<br />

Brine water<br />

Brine water<br />

15<br />

<strong>20</strong><br />

2.50<br />

3.50<br />

63.22<br />

84.25<br />

0.224<br />

0.296<br />

Exergetic, thermodynamic analysis data for GSHP system R22<br />

Component<br />

Éxdest<br />

(kw)<br />

Uttilized<br />

power(kw)<br />

<br />

(KW)<br />

<br />

(KW)<br />

<br />

%<br />

IP<br />

(w)<br />

Compressor 0.4792 1.3522 0.873 1.3522 64.56 169.3<br />

Condenser 0.1026 4 0.1481 0.5276 80.29 <strong>20</strong>.2<br />

Exp valve 0.1326 _ 0.7971 .9297 85.74 18.9<br />

Evaporator 0.31 2.7576 .0934 .2<strong>19</strong>7 42.51 179.9<br />

Fan coil unit .3081 4 0.11 0.4181 26.30 227.1<br />

GHE 0.0185 2.7567 .0935 0.11<strong>20</strong> 83.48 3<br />

GSHP 1.0275 8.1089 2.1816 3.0223 72.18 388.3<br />

Overall<br />

system<br />

1.3541 14.8656 2.3851 3.5544 67.41 618.4<br />

Estimation <strong>of</strong> reduction in co2 emission for R22<br />

Assuming that the approximate heat load for a room in is about 4 kw and a heater <strong>of</strong> 4 kw capacity is used for<br />

space heating for 6 hr during a day , the total electricity consumed by a heater during three months <strong>of</strong> winter<br />

=4*6*30*3=2160 kw hr<br />

130