Proceedings <strong>of</strong> the National Conference on<br />

Trends and Advances in Mechanical Engineering,<br />

<strong>YMCA</strong> <strong>University</strong> <strong>of</strong> <strong>Science</strong> & <strong>Technology</strong>, Faridabad, Haryana, Oct <strong>19</strong>-<strong>20</strong>, <strong>20</strong>12<br />

The total light wattage is obtained from the ratings <strong>of</strong> all lamps installed, both for general illumination and for<br />

display use.<br />

The use factor is the ratio <strong>of</strong> the wattage in use, for the condition under which the load estimate is being made,<br />

to the total installed wattage. For commercial applications, such as stores, the use factor is unity<br />

The special allowance factor is for fluorescent fixtures that are either ventilated or installed so that only part <strong>of</strong><br />

the heat goes to the conditioned space. For fluorescent fixtures, the special allowance factor primarily accounts<br />

for ballast losses and can be as high as 2.<strong>19</strong> for 32W single-lump high-output fixtures on 227V circuits.<br />

Heat Gain from Occupants<br />

Human beings give <strong>of</strong>f heat at a metabolic rate, which depends on their rate <strong>of</strong> working. The sensible and latent<br />

heat proportion <strong>of</strong> the heat librated for any given activity depends on the value <strong>of</strong> the ambient dry bulb<br />

temperature; the lower the dry bulb temperature the larger the proportion <strong>of</strong> sensible heat dissipated.<br />

Deciding on the density <strong>of</strong> occupation is usually a problem for the designer. A normal density for an <strong>of</strong>fice<br />

block is 9m 2 per person, as an average for the whole conditioned floor area. The density <strong>of</strong> occupation may be as<br />

high as <strong>20</strong>m 2 per person in executive <strong>of</strong>fices or as low as 6m 2 per person in open <strong>of</strong>fice areas.<br />

Heat Gain from Equipments<br />

Instantaneous heat gain from equipment operated by electric motors within a conditioned space is calculated as<br />

Where<br />

Qem -heat equivalent <strong>of</strong> equipment operation, W<br />

P-motor power rating, W<br />

E M -motor efficiency, decimal fraction