17.2.2 PLC Outputs<br />

Check the PLC outputs as follows:<br />

Connect the test unit between LE and PLC or between LE and PL.<br />

Set the <strong>TNC</strong> as follows:<br />

SERVICE MANUAL <strong>TNC</strong> <strong>407</strong>/<strong>415</strong><br />

Issue: 01.09.1995<br />

Page 81<br />

Prepare <strong>TNC</strong> for code number input<br />

Enter code number, acknowledge with ENT<br />

Soft key >TABLE< to display the tables<br />

Soft key >OUTPUT< to display the output table<br />

Now the logic states of the outputs are displayed on the screen. The states of the screen display must<br />

correspond to those of the test unit. If there is a difference, test the connecting cable for short circuit and<br />

measure the output current at interface (max. 100 mA for LE outputs, max. 1.2 A for PL outputs). If the<br />

output current is not exceeded and the connecting cable is in order, the output board is probably defective<br />

(00 to 030 of processor board, 032 to 062 of I/O board PL 400).<br />