10.5 MAPWAY/ETHWAY Network and Station Number P100<br />

Description<br />

10 - 10 en-938818/6<br />

Category Communication<br />

Type 0 Hexadecimal on 8 bits<br />

No. of words 8<br />

Configures the station according to the Telemecanique series 7 addressing system.<br />

The network and station <strong>num</strong>bers physically identify a unit on the MAPWAY or ETHWAY network. Refer to the<br />

MAPWAY-ETHWAY documentation for further details.<br />

Specifies the notation type (Intel or Motorola) used for transmission of words or long words over the network.<br />

REMARK: If the interface is present in the rack and <strong>parameter</strong> P100 is not set, the DEF LED<br />

on the front of the interface flashes and the message «PARAMETER P100 WORD<br />

0 INCORRECT» is displayed in the «Error message» page.<br />

Principle<br />

Word N0<br />

Sets the network <strong>num</strong>ber (Telemecanique series 7 addressing). The default value is $FF.<br />

Word N1<br />

Sets the station <strong>num</strong>ber (Telemecanique series 7 addressing). The default value is $FF.<br />

Word N2<br />

Sets the notation type (Intel or Motorola).<br />

Set to 0 for Intel notation.<br />

Set to 1 for Motorola notation.<br />

Order of Byte Transmission Over the Network<br />

Byte 1 Byte 2 Byte 3 Byte 4<br />

Intel notation Word Low byte, LSBs Low byte, MSBs<br />

Long word Low byte, LSBs Low byte, MSBs High byte, LSBs High byte, MSBs<br />

Motorola notation Word Low byte, MSBs Low byte, LSBs<br />

Long word High byte, MSBs High byte, LSBs Low byte, MSBs Low byte, LSBs