<strong>System</strong> <strong>Manual</strong> – DOP11A <strong>Operator</strong> <strong>Terminal</strong>s<br />

Installation<br />

RS-485 connection (DOP11A-10 and DOP11A-30 only)<br />

If the DOP11A-10 operator terminal is connected with the frequency inverters via RS-<br />

485, you will have to activate the terminating resistor in the 25-pin Sub-D connector of<br />

the DOP11A-10 (jumper between pin 6 and pin 19) in case the operator terminal is the<br />

first or last station.<br />

There must not be any difference of potential between the units connected using the RS-<br />

485. Take suitable measures to avoid a potential displacement, e.g. by connecting the<br />

unit ground connectors using a separate lead.<br />

4<br />