<strong>Engineering</strong> <strong>Standards</strong><br />

F. The Inlet Spreadsheet provided in Figure 2 shall be provided with the construction plans for<br />

review by the <strong>City</strong>. A description <strong>of</strong> each <strong>of</strong> the columns shown in the inlet spreadsheet is<br />

provided below:<br />

• Column 1: Design Point for Inlet<br />

• Column 2: Inlet number<br />

• Column 3: Location <strong>of</strong> inlet by storm drain station number<br />

• Column 4: Drainage area designation for incremental area<br />

• Column 5: Drainage area size (acres)<br />

• Column 6: Run<strong>of</strong>f coefficient (C)<br />

• Column 7: Time <strong>of</strong> concentration (minutes)<br />

• Column 8: 100-year intensity (in/hr)<br />

• Column 9: 100-year run<strong>of</strong>f, Q=CIA (cfs)<br />

• Column 10: 100-year carryover flow from upstream inlet (cfs)<br />

• Column 11: 100-year total gutter flow (Column 9 + Column 10) (cfs)<br />

• Column 12: Percentage <strong>of</strong> flow traveling from lower station side <strong>of</strong> sag inlet based on<br />

percentage <strong>of</strong> drainage area and carryover flow from that side (cfs)<br />

• Column 13: Percentage <strong>of</strong> flow traveling from higher station side <strong>of</strong> sag inlet based on<br />

percentage <strong>of</strong> drainage area and carryover flow from that side (cfs)<br />

• Column 14: 100-year total gutter flow reaching the lower station side <strong>of</strong> the sag inlet<br />

(Column 11 times Column 12) (cfs)<br />

• Column 15: 100-year total gutter flow reaching the higher station side <strong>of</strong> the sag inlet<br />

(Column 11 times Column 13) (cfs)<br />

• Column 16: Longitudinal slope <strong>of</strong> the approach gutter. For sag inlets, half the longitudinal<br />

slope <strong>of</strong> the approach gutter on the lower station side <strong>of</strong> the inlet (S 0 ) (ft/ft)<br />

• Column 17: Not used for on-grade inlets. For sag inlets, half the longitudinal slope <strong>of</strong> the<br />

approach gutter on the higher station side <strong>of</strong> the inlet (S 0 ) (ft/ft)<br />

• Column 18: Street crown section type (straight crown [“ro<strong>of</strong>top”] or parabolic)<br />

• Column 19: Roadway cross slope “Sx” (%)<br />

• Column 20: Manning’s roughness coefficient (n) for pavement (0.0175 for concrete<br />

pavement)<br />

Section 4 – Drainage Design Requirements May 2012 Page 4-16