<strong>Engineering</strong> <strong>Standards</strong><br />

5.2.6 Wastewater Main Materials<br />

A. Polyvinyl Chloride (PVC) Wastewater Pipe<br />

1. PVC non-pressure rated gravity wastewater mains from 6” to 15” in diameter shall be SDR<br />

35 (if less than 15’ deep) or SDR 26 (if 15’ or deeper) (ASTM D3034) .<br />

2. PVC non-pressure rated gravity wastewater mains 18” in diameter and greater shall have a<br />

minimum pipe stiffness <strong>of</strong> 46 psi or 115 psi and be manufactured in accordance with ASTM<br />

F679 (solid wall).<br />

3. PVC pressure rated gravity wastewater mains and force mains from 6” to 12” in diameter<br />

shall be SDR 26 (ASTM D2241) with a minimum pressure rating <strong>of</strong> 160 psi.<br />

4. PVC pressure rated gravity wastewater mains and force mains greater than 12” in diameter<br />

shall be AWWA C905 DR25 with a minimum pressure rating <strong>of</strong> 165 psi.<br />

5. PVC pr<strong>of</strong>ile wall pipe will not be allowed.<br />

B. Fiberglass (Glass-Fiber-Reinforced Thermosetting Resin) Pipe<br />

1. Fiberglass non-pressure rated gravity wastewater mains 18” in diameter and greater shall be<br />

in accordance with ASTM D3262 with a minimum pipe stiffness <strong>of</strong> 46 psi and Class “B-2”<br />

embedment in accordance with NCTCOG Item 504.5 and Standard Drawing 3020.<br />

2. Fiberglass pressure rated gravity wastewater mains and force mains 18” in diameter and<br />

greater shall be in accordance with ASTM D3754 with a minimum pressure rating <strong>of</strong> 150 psi<br />

and Class “B+” embedment in accordance with NCTCOG Item 504.5 and Standard Drawing<br />

3020.<br />

C. Vitrified clay pipe will not be allowed.<br />

5.2.7 Wastewater Service Laterals<br />

The sizes and locations <strong>of</strong> laterals shall be designated as follows:<br />

A. Wastewater service laterals for single-family residential shall be a minimum <strong>of</strong> 4” in diameter.<br />

Laterals shall be installed 10’ downstream from the center <strong>of</strong> the lot and have a minimum<br />

separation distance <strong>of</strong> 10’ separation from the water service.<br />

B. Wastewater service laterals for multiple units, apartments, local retail and commercial<br />

developments shall be a minimum <strong>of</strong> 6” in diameter.<br />

C. Wastewater service laterals for manufacturing and industrial shall be a minimum <strong>of</strong> 8”.<br />

D. Manholes are required on 6” and larger wastewater service laterals where they connect to the<br />

main line.<br />

E. Wastewater service laterals shall not be attached to wastewater mains that are deeper than 12’.<br />

Deep cut or drop connections are not be permitted.<br />

F. Each building shall have only one wastewater service lateral, except duplexes which shall have<br />

two wastewater service laterals independently attached to the main.<br />

Section 5 – Water & Wastewater Design Requirements May 2012 Page 5-12