F. Fire hydrants shall be provided every 500’ within residential developments as measured along the<br />

route that a fire hose is laid by a fire apparatus.<br />

G. The fire hydrant shall not be located in the sidewalk.<br />

H. Fire hydrant valves shall be positioned to one side <strong>of</strong> the fire hydrant pumper nozzle.<br />

I. Fire hydrants required to supplement water supply for automatic fire protection systems shall be<br />

located within 100’ <strong>of</strong> the Fire Department connection for such system.<br />

J. Additional requirements for fire hydrant installation adjacent to, and along fire lanes is as<br />

follows:<br />

1.<br />

Multi-family<br />

a. Fire hydrants shall be located every 300’ as measured along the route that a fire hose is<br />

laid by a fire apparatus.<br />

b. Fire hydrants shall be located outside the radius <strong>of</strong> the fire lane and at least 35’ from all<br />

buildings.<br />

c. A minimum <strong>of</strong> two fire hydrants shall be located within 500’ <strong>of</strong> the front <strong>of</strong> any building<br />

as measured along the route that a fire hose is laid by a fire apparatus.<br />

2.<br />

Commercial<br />

a. Fire hydrants shall be located within 150’ <strong>of</strong> the main entrance.<br />

b. Fire hydrants shall be located outside the radius <strong>of</strong> the fire lane and at least 35’ from all<br />

buildings.<br />

c. A minimum <strong>of</strong> two fire hydrants shall be located within 300’ from the front <strong>of</strong> any<br />

building as measured along the route that a fire hose is laid by a fire apparatus.<br />

K. 6 inch water mains shall be installed such that not more than one hydrant will be between<br />

intersecting lines.<br />

L. 8” water mains shall be installed such that not more than two fire hydrants will be between<br />

intersecting lines.<br />

M. Fire hydrants on private property shall be located within easements and protected by curb stops or<br />

bollards, the maintenance <strong>of</strong> which shall be the responsibility <strong>of</strong> the property owner. The property<br />

owner is responsible for keeping the curb stops or bollards in place.<br />

N. Fire hydrants on private property shall be accessible to the Fire Department at all times.<br />

O. Fire hydrants location is subject to approval <strong>of</strong> Fire Department.<br />

5.1.10 Connections to Existing Water Mains<br />

A. Connections to 12” water mains and larger shall be made with a pipe a minimum <strong>of</strong> one size<br />

smaller than the line being tapped.<br />

Section 5 – Water & Wastewater Design Requirements May 2012 Page 5-7