SECTION 331218<br />

BUTTERFLY VALVES<br />

PART 1 – GENERAL<br />

1.01 DESCRIPTION<br />

A. All material, labor, equipment, tools and superintendence necessary to furnish and install<br />

Butterfly Valves For Potable Water Systems in accordance with Public Works Construction<br />

<strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.6.5.<br />

1.02 REFERENCES<br />

A. AWWA C504, AWWA Standard for Rubber-Seated Butterfly Valves, Latest Revision<br />

B. Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.6.5<br />

C. <strong>City</strong> <strong>of</strong> <strong>Frisco</strong>’s Standard Detail for Butterfly Valves.<br />

PART 2 – PRODUCTS<br />

2.01 MATERIALS<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.6.5.<br />

B. Refer to <strong>City</strong> <strong>of</strong> <strong>Frisco</strong>’s Approved Material List.<br />

C. Butterfly valves shall be Mueller Model Series 3211 or M&H Model Series 4500/1450 or<br />

approved equal. Valves shall be Class 250.<br />

D. Valve boxes shall be three (3) piece screw type cast iron <strong>of</strong> the extension type. The three (3)<br />

pieces shall consist <strong>of</strong> the top section, bottom section and cover.<br />

PART 3 – EXECUTION<br />

3.01 INSTALLATION<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.6.6.<br />

B. All valve locations shall be marked with a “V” sawcut on the curb or pavement. The “V”<br />

shall point to the location <strong>of</strong> the valve as follows:<br />

Valve in pavement<br />

Valve outside pavement<br />

Upright “V”<br />

Upside Down “V”<br />

C. The butterfly valve operator shall face away from the curb line on all installations.<br />

D. Valve boxes over four feet (4’) deep shall require extensions. Valve box extensions shall be<br />

cast iron. PVC pipe is not allowed.<br />

<strong>City</strong> <strong>of</strong> <strong>Frisco</strong> May 2012<br />

Standard Technical Specification Butterfly Valves 331218-1