B. A tapping saddle shall be used to connect service lines to pipe mains.<br />

C. The service pipe shall be placed at a minimum depth <strong>of</strong> twenty-four inches (24”) under the<br />

finished grade except where the service pipe shall pass under the curb. At this point the<br />

service pipe shall be a minimum <strong>of</strong> twenty-four inches (24”) under the top <strong>of</strong> curb or a<br />

minimum <strong>of</strong> six inches (6”) under the bottom <strong>of</strong> the curb and gutter section, or lime stabilized<br />

subgrade whichever is greater.<br />

D. Excessive bending <strong>of</strong> the service pipe, which will injure or reduce the cross sectional area <strong>of</strong><br />

the pipe, will not be permitted.<br />

E. The length <strong>of</strong> the service pipe shall extend from the main to a point two feet (2’) back <strong>of</strong> the<br />

street curb or to the property line if no curb exists, unless shown otherwise on the plans.<br />

F. The service pipe shall be continuous with no fittings under paving.<br />

G. If there is a curb, the curb shall be sawcut with “I” and marked with good quality blue paint at<br />

the point where the service pipe passes the curb.<br />

H. Sand embedment shall be required two feet (2’) on either side <strong>of</strong> the service saddle all the<br />

way around the water main.<br />

PART 4 – MEASUREMENT AND PAYMENT<br />

4.01 MEASUREMENT<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.10.3.2.2.<br />

4.02 PAYMENT<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.10.3.2.2.<br />

END OF SECTION<br />

<strong>City</strong> <strong>of</strong> <strong>Frisco</strong> May 2012<br />

Standard Technical Specification Water Service Connections 331213-2