SECTION 331219<br />

FIRE HYDRANTS<br />

PART 1 – GENERAL<br />

1.01 DESCRIPTION<br />

A. All material, labor, equipment, tools and superintendence necessary to furnish and install<br />

Fire Hydrants in accordance with Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th<br />

Edition, Item 502.3.<br />

1.02 REFERENCES<br />

A. AWWA C502, AWWA Standard for Dry-Barrel Fire Hydrants, Latest Revision<br />

B. Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.3<br />

C. <strong>City</strong> <strong>of</strong> <strong>Frisco</strong>’s Standard Details for Fire Hydrants.<br />

PART 2 – PRODUCTS<br />

2.01 MATERIALS<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.3.<br />

B. Refer to <strong>City</strong> <strong>of</strong> <strong>Frisco</strong>’s Approved Material List.<br />

C. Fire hydrants shall be Waterous Pacer 5 ¼” Model WB67-250 or American Darling 5 ¼”<br />

Model B-84-B or approved equal.<br />

D. Hydrant barrel inside diameter shall not be less than 7 ¼”.<br />

E. All hydrants shall be equipped with two (2) hose nozzles and one (1) steamer nozzle. The<br />

hose nozzles shall be two and one-half inches (2 ½”) nominal I.D. National Standard<br />

Thread. Pumper nozzle shall be four inches (4”) nominal I.D. National Standard Thread.<br />

All nozzles shall be mechanically attached.<br />

F. All five hydrants shall open by turning to the left (counter-clockwise).<br />

G. All hydrants shall be <strong>of</strong> the breakable type.<br />

H. All hydrants shall have a 4 mil epoxy coating on the interior <strong>of</strong> the shoe.<br />

PART 3 – EXECUTION<br />

3.01 INSTALLATION<br />

A. Refer to Public Works Construction <strong>Standards</strong>, NCTCOG, 4 th Edition, Item 502.3.2.<br />

<strong>City</strong> <strong>of</strong> <strong>Frisco</strong> May 2012<br />

Standard Technical Specification Fire Hydrants 331219-1