<strong>Engineering</strong> <strong>Standards</strong><br />

Table 5.3: Minimum and Maximum Grades for Wastewater Mains*<br />

Size <strong>of</strong> Pipe<br />

(inches)<br />

Minimum Slope in<br />

(Percent)<br />

Maximum Slope in<br />

(Percent)<br />

8 0.33 8.40<br />

10 0.25 6.23<br />

12 0.20 4.88<br />

15 0.15 3.62<br />

18 0.11 2.83<br />

21 0.09 2.30<br />

24 0.08 1.93<br />

27 0.06 1.65<br />

30 0.055 1.43<br />

33 0.05 1.26<br />

36 0.045 1.12<br />

39 0.04 1.01<br />

>39 ** **<br />

*The slopes were calculated using Manning’s Equation and a roughness coefficient<br />

<strong>of</strong> 0.013.<br />

**For lines larger than 39” in diameter, the slope shall be determined using the<br />

following equation.<br />

where:<br />

V = velocity <strong>of</strong> flow in wastewater main (fps)<br />

n = roughness coefficient <strong>of</strong> the wastewater main<br />

R = hydraulic radius <strong>of</strong> the wastewater main (ft), which is equal to<br />

the area <strong>of</strong> the flow divided by the wetted perimeter (R=A/P)<br />

S = Slope <strong>of</strong> the hydraulic gradient (ft/ft)<br />

5.2.3 Separation Distance between Wastewater and Water Mains<br />

A. The separation distance between wastewater and water mains or other appurtenances is governed<br />

by Title 30 <strong>of</strong> the Texas Administrative Code, Part 1, Chapter 217, Subchapter C, Rule 217.53(d).<br />

B. Wastewater mains shall be installed in trenches separate from water mains.<br />

C. Wastewater mains shall have a minimum separation distance <strong>of</strong> 9’ in all directions from water<br />

mains. All separation distances shall be measured from the outside surface <strong>of</strong> each <strong>of</strong> the<br />

respective facilities.<br />

D. If the minimum separation distances cannot be achieved for crossing water and wastewater mains,<br />

the separation distances may be reduced under two scenarios:<br />

1. The wastewater main has a minimum pressure rating <strong>of</strong> 150 psi.<br />

2. The water or wastewater main is cased for a minimum <strong>of</strong> 18’ with a casing pipe having a<br />

minimum pressure rating <strong>of</strong> 150 psi.<br />

Section 5 – Water & Wastewater Design Requirements May 2012 Page 5-10