<strong>Engineering</strong> <strong>Standards</strong><br />

Section 9 – Structural Design Requirements<br />

9.01 General<br />

A. The Design Engineer <strong>of</strong> record shall bear the sole responsibility for meeting the engineering<br />

standard <strong>of</strong> care for all aspects <strong>of</strong> the design and providing a design that’s required by the sitespecific<br />

conditions and intended use <strong>of</strong> the facilities.<br />

B. For the purposes <strong>of</strong> this section <strong>of</strong> the <strong>Engineering</strong> <strong>Standards</strong>, the following items shall be<br />

considered structures: bridges, foundations, retaining walls (structural and gravity), headwalls and<br />

wingwalls, culverts, slopes and embankments, and screening walls.<br />

C. The <strong>City</strong>’s review <strong>of</strong> any structural design is limited to determining whether the construction<br />

plans are in general compliance with the <strong>City</strong>’s Master Plans and <strong>Engineering</strong> <strong>Standards</strong>. The<br />

<strong>City</strong>’s review and release <strong>of</strong> the construction plans does not represent that the <strong>City</strong> has reengineered<br />

or verified the engineering <strong>of</strong> the proposed improvements.<br />

D. The structural design must be signed and sealed by a structural engineer or civil engineer<br />

competent in structural engineering licensed in the State <strong>of</strong> Texas. The Design Engineer is<br />

responsible for all engineering and recognizes that specific site circumstances or conditions may<br />

require improvements constructed to exceed minimum standards contained in the <strong>City</strong>’s<br />

<strong>Engineering</strong> <strong>Standards</strong>. The Design Engineer is responsible for the applicability and accuracy <strong>of</strong><br />

the construction plans and specifications.<br />

E. Walls shall be permitted and constructed in accordance with all requirements <strong>of</strong> these<br />

<strong>Engineering</strong> <strong>Standards</strong>. Third-party inspections shall be performed during construction, and<br />

reports provided to the <strong>City</strong>. A third-party shall certify wall was constructed in general<br />

compliance with the <strong>City</strong>-approved plans and specifications, and a certification shall be provided<br />

to the <strong>City</strong>.<br />

9.02 Code Requirements<br />

A. All structural design shall comply with the <strong>City</strong>’s currently adopted version <strong>of</strong> the International<br />

Building Code.<br />

B. The design and construction <strong>of</strong> structural concrete for buildings and where applicable in nonbuilding<br />

structures shall be provided in accordance with the requirements <strong>of</strong> the current version <strong>of</strong><br />

“Building Code Requirements for Structural Concrete (ACI 318)” as published by the American<br />

Concrete Institute.<br />

C. Placing reinforcing steel in reinforced concrete structures shall be provided in accordance with<br />

the requirements <strong>of</strong> the current version <strong>of</strong> the “ACI Detailing Manual (ACI 315)” as published by<br />

the American Concrete Institute.<br />

D. The design and construction <strong>of</strong> concrete tanks, reservoirs, and other structures commonly used in<br />

water and wastewater treatment works where dense, impermeable concrete with high resistance to<br />

chemical attack is required shall be provided in accordance with the requirements <strong>of</strong> the current<br />

version <strong>of</strong> “Environmental <strong>Engineering</strong> Concrete Structures (ACI 350)” as published by the<br />

American Concrete Institute. This code places special emphasis on structural design that<br />

minimizes the possibility <strong>of</strong> cracking and accommodates vibrating equipment and other special<br />

loads. ACI 350’s minimum requirements for proportioning <strong>of</strong> concrete, placement, curing, and<br />

Section 9 – Structural Design Requirements May 2012 Page 9-2