G. All mains installed for future developable areas shall include wastewater service laterals; the use<br />

<strong>of</strong> boots will not be permitted.<br />

H. All wastewater service laterals crossing water mains shall conform to the requirements <strong>of</strong> the<br />

TCEQ Chapter 217, Subchapter C, Rule 217.53(d), latest revision, or Section 5.2.3 <strong>of</strong> this<br />

standard.<br />

5.2.8 Manholes and Cleanouts<br />

A. Manholes shall be installed at all changes in grade and direction, and have a maximum spacing <strong>of</strong><br />

500’.<br />

B. Spacing between a manhole and an upstream cleanout shall be a maximum <strong>of</strong> 250’. A cleanout<br />

or manhole shall be located at the end <strong>of</strong> a wastewater main.<br />

C. Manholes on curved wastewater mains shall be located at the P.C. or P.T. <strong>of</strong> the curve and have a<br />

maximum spacing <strong>of</strong> 300’ along the curve.<br />

D. Manholes shall be constructed <strong>of</strong> monolithic, cast-in-place concrete, precast concrete or<br />

fiberglass.<br />

E. Manholes shall be concentric type unless otherwise approved by the Director <strong>of</strong> <strong>Engineering</strong><br />

Services.<br />

F. Drop manholes shall be required when the inlet pipe flow line elevation is more than 24” above<br />

the outlet pipe flow line elevation. Drops shall be outside the manhole unless otherwise approved<br />

by the Director <strong>of</strong> <strong>Engineering</strong> Services.<br />

G. Manholes shall be sized as follows:<br />

1. 4’ in diameter for 8”, 10”, and 12” pipe.<br />

2. 5’ in diameter for 15”, 18”, 21”, 24” and 27” pipe.<br />

3. 6’ in diameter for 30” and 36” pipe.<br />

4. 5’ in diameter minimum for manholes deeper than 15’.<br />

H. Where more than three manholes in sequence are to be bolted and sealed, every third manhole<br />

shall be vented 2’ above the 100-year floodplain elevation or 10’ above the adjacent ground line,<br />

whichever is higher. The Engineer shall provide the elevation <strong>of</strong> the 100-year floodplain on the<br />

pr<strong>of</strong>ile.<br />

I.<br />

Construct manholes within 30’ <strong>of</strong> each end <strong>of</strong> wastewater mains that are installed by other than<br />

open cut and within 30’ <strong>of</strong> each end <strong>of</strong> aerial crossings.<br />

J. Manholes shall not be located in parking spaces.<br />

K. A manhole with pipes <strong>of</strong> different sizes must have the tops <strong>of</strong> the pipes at the same elevation and<br />

flow channels in the invert sloped on an even slope from pipe to pipe.<br />

Section 5 – Water & Wastewater Design Requirements May 2012 Page 5-13