“O’ZLITINEFTGAZ” PC<br />

PFS “<strong>Surgil</strong> field complex costruction with valuable<br />

components retrieval”<br />

2.9 INFRASTRUCTURE OBJECTS<br />

Power supply and electrochemical protection<br />

Technological process on <strong>Surgil</strong> CGTU is continuous. According to RD 51-122-87<br />

and PUE-86g, collectors of CGTU by degree of power supply reliability concern to I<br />

category consumers.<br />

Total loads according to the executed calculations make:<br />

Table 10 - Design loads<br />

Name<br />

Installed capacity,<br />

kV<br />

Design<br />

capacity,<br />

kV<br />

Annual electric<br />

power consumption<br />

thous.kV.h.<br />

CGTU primary function zone 256.66 188.56 859.376<br />

CGTU secondary function zone 165.75 116.37 367.17<br />

EСCP GGS -1. 2. 3 45 45 394.2<br />

EСCP of wells loops 144 144 1261.44<br />

Pump station over artesian well 22 13.64 143.00<br />

Total 633.41 507.57 3025.186<br />

Because of absence in the region of CGTU area construction of reliable source for<br />

power supply of CGTU, EСCP consumers, there is provided installation of own source of<br />

power supply on the area - gas-piston power stations of РG475В mark, made by FG Wilson<br />

company, by capacity of 380kW in number of 3 sets.<br />

For power supply of pump station over artesian wells there is provided by the project<br />

the installation of packaged switchyard MKTP-63/10/0.4U1 with transformer by capacity<br />

63kVA on each well. External power supply is feed from OTL 10kV of EСCP gas pipeline<br />

and condensate line of <strong>Surgil</strong> CGTU– Akchalak GCC.<br />

The main consumers of the electric power of CGTU area are: motors of technological<br />

installations (pumps, fans, electric gate valves of pipelines); CEA devices; electric lighting<br />

installations. Motors are, basically, asynchronous, with a short-circuited rotor for voltage<br />

380V AC. They are completed on the basis of required power of mechanisms. Motors<br />

version is accepted depending on environment of premises and external installations (in the<br />

normal, protected and explosion-proof versions).<br />

Voltage of the power electric equipment network is 380/220V. Voltage of lighting<br />

network is 220V.<br />