After the sewage aeration tanks in the water settles in the secondary clarifier. Purified<br />

water is then chlorinated and then enters the post-treatment in the evaporation ponds, as the<br />

quality of its still does not conform to clear the pond cultural purpose<br />

Quality of treated water is tentatively as follows<br />

рН - 6,5-8,5<br />

BOD5, mg / l - 25<br />

COD mg / l - no more 120<br />

Phenols, mg / l - less 0,15<br />

Petroleum products, mg / l - 2,0<br />

Benzene, mg / l - 0,05<br />

Benzapyrene, mg / l - 0,05<br />

Ammonia nitrogen, mg / l - less 5,0<br />

Suspended solids, mg / l - 20<br />

As can be seen from the above qualities of treated wastewater, they still contain quite a lot<br />

of residual amounts of organic substances that are usually difficult to<br />

oxidizing substances.<br />

The variant of dumping of industrial waste treatment facilities after absorbing in the deep<br />

horizons in coordination with the hydrogeological services.<br />

Water on the residential village for drinking and fire protection needs is supplied through a<br />

pipeline 4 km long (Figure 13).<br />

Water use residential village is:<br />

- drinking needs - 432.2 m3/day<br />

On the platform were designed waterworks consisting of:<br />

- pumping station drinking, firefighting purposes;<br />

- water storage tanks of drinking-fire destination for up to 400 m3 (2 pcs.)<br />

- filter-absorbers.<br />

Supply of water for drinking - fire needs of - 674 m3. Structurally, the installation made<br />

two tanks of 400 m3 (water supply in one conduit).<br />

Таble 14 – Equipment in the pumping station drinking - firefighting purposes<br />

Mark<br />

Pump<br />

Pump<br />

K100-65-200<br />

(fire-fighting<br />

purposes)<br />

Para-<br />

Meters Quantity, Power,<br />

Rasstroke<br />

Ontime<br />

pcs kW Type of electric<br />

motor<br />

Power<br />

, kW<br />

м 3 /час м раб рез.<br />

100 50 1 1 2900 4АМ160S2У32 30<br />