TROUBLESHOOTING<br />

I<br />

GB GB F D<br />

4.1<br />

TABLE OF PROBLEMS AND SOLUTIONS<br />

Effect<br />

After turning on the unit, alarm E41<br />

appears on the microcomputer display<br />

(manual re-arm)<br />

There are unusual noises or vibrations<br />

coming from the hydraulic circuit<br />

When the chiller is turned on (summer/<br />

winter selector in summer position), the<br />

microprocessor remains switched off and<br />

at the same time, the orange flushing<br />

warning light flashes.<br />

Alarm E 01 appears (manual re-arm)<br />

Alarm E 02 appears (5 times in an hour,<br />

automatic and manual re-arm)<br />

Alarm E 05 appears (manual re-arm)<br />

Cause<br />

The water does not circulate well in the<br />

system.<br />

There is air inside the circuit.<br />

The following could have intervened:<br />

• the minimum level float<br />

• the maximum level float<br />

The high-pressure pressure switch has<br />

intervened.<br />

The low pressure alarm has been<br />

triggered<br />

Too much anti-freeze in the circuit<br />

The anti-freeze minimum temperature<br />

alarm has intervened.<br />

The outlet water temperature has fallen<br />

below 3°C.<br />

Solution<br />

Check that: the interception valves are<br />

open, that the 3-way valve for the hot-cold<br />

deviation is in the correct position, that<br />

there are no air bubbles in the circuit,<br />

that at least one of the user-units has the<br />

circuit open or is fitted with a three-way<br />

valve, that the external sieve filter is not<br />

blocked, that the water pressure in the<br />

system is correct, that the circulation<br />

pump is working correctly (unblock if<br />

necessary)<br />

Bleed the air both with the external units<br />

and the vent on the machine inertial tank<br />

and return the circuit to the correct load<br />

pressure.<br />

Check that the suction pressure<br />

(hydraulic circuit return) is more than 0.6<br />

BAR with the pump ON.<br />

Check that the mains water supply is<br />

open. Check that the water drain is<br />

connected correctly and there are no<br />

obstructions.<br />

Open the front panel and the front<br />

protection of the cooling water tank.<br />

Check: with a tester the correct working<br />

efficiency of the floats, the drainage pump,<br />

the hot water solenoid valve (that must<br />

only open with the go-ahead of the level fl<br />

oat that is between the minimum and<br />

maximum).<br />

Check that there is mains water supply<br />

Ensure that the air inlet and outlet pipes<br />

and the external grills are not blocked.<br />

If the unit has already been used for more<br />

than a year, clean the condenser and<br />

check the working efficiency of the<br />

cooling water recirculation and drainage<br />

pumps.<br />

Ensure that the hydraulic circuit closing<br />

valves are open.<br />

Check that there is a good water<br />

circulation (no air in the system, the<br />

deviation valves are in the correct<br />

position, sieve filters are clean etc.)<br />

Check the inflow of the coolant.<br />

Check that the rooms are not too cold for<br />

the chiller operation (T< 10 °C).<br />

Check that there is not an excessive<br />

quantity of anti-freeze (more than 40%)<br />

in the hydraulic circuit.<br />

Check that there is nothing that impedes<br />

the good water circulation in the system<br />

(air, valves partially closed, sieve filter<br />

blocked, etc).<br />

Check that the thermal difference between<br />

inlet and outlet is between 4 and 6°C -<br />

checking the parameter t02 (see<br />

paragraph 3.2.2)"<br />

Check the correct positioning of the inlet<br />

probe checking that the temperature<br />

shown by the controller on the display is<br />

consistent with the temperature of inlet<br />

water to the chiller<br />