E P GB NL<br />

GR 4<br />

Effect<br />

Alarm E 40 appears (automatic re-arm)<br />

Alarm E 06 appears (automatic re-arm)<br />

Cause<br />

The inlet water temperature probe is faulty<br />

or not correctly connected.<br />

The antifreeze/outlet water temperature<br />

probe is faulty or not correctly connected.<br />

Solution<br />

Check the connection and if necessary<br />

replace the probe.<br />

Check the connection and if necessary<br />

replace the probe.<br />

Alarm E 46 appears (automatic re-arm)<br />

The desired water temperature is not<br />

reached within a reasonable time<br />

The machine vibrates excessively<br />

The ventilation noise is excessive<br />

There are leaks of water from the<br />

ventilation pipes<br />

The inlet water temperature has exceeded<br />

35°C.<br />

The thermal load is excessive.<br />

The air inlet or expulsion pipes or the<br />

grills are blocked or too long causing a<br />

fall in the volume of air.<br />

The wall fixings or the floor mounting<br />

positioning are not correct. The pipes have<br />

no anti-vibration joints. The compressor<br />

has moved or the tubes have deformed<br />

during the transport.<br />

There are cracks In the joints or along the<br />

air outlet pipes. The union closing plugs<br />

are missing.<br />

Inadequate drainage has been performed<br />

or the air pipes for the condenser are too<br />

long<br />

If a boiler is installed in the system, check<br />

the system deviator valves.<br />

Check the dimensioning of the system<br />

and the number of connected terminals.<br />

Check the path of the pipes and the<br />

presence of obstacles in proximity to the<br />

inlet and outlet grills<br />

Check that the pipes are not pressing<br />

against parts of the frame (transmitting<br />

vibrations).<br />

Connect correctly the air pipes to the<br />

unions on the machine. Check that all<br />

the closing plugs have been well fixed<br />

onto the unused unions.<br />

Check the joints between the various<br />

pipes and between the pipes and the<br />

unions on the machine.<br />

If the unit has been functioning for some<br />

time, clean the condenser.<br />

Check the correct dimensions of the<br />

condenser air inlet and outlet pipes (see<br />

paragraph 2.2.5).<br />

Water is dripping out of the outside grills<br />

The unit does not work, the control panel<br />

display is switched off, the yellow washing<br />

warning light flashes 1 second ON/1<br />

second OFF<br />

The unit does not work, the control panel<br />

display is switched off, the yellow washing<br />

warning light flashes 1 second ON/3<br />

seconds OFF<br />

The unit does not work, the control panel<br />

display is switched off, the yellow washing<br />

warning light flashes rapidly 400<br />

milliseconds ON/400 milliseconds OFF<br />

The unit is working normally, the yellow<br />

washing warning light flashes 3 seconds<br />

ON/3 seconds OFF<br />

There is not a good water circulation in<br />

the system<br />

For more than 5 minutes the unit is trying<br />

to fill the condensation collection tank<br />

without reaching the level float.<br />

The maximum level float has intervened<br />

more than 3 times in an hour.<br />

The micro-switch 1 (condenser cleaning<br />

function) is switched to ON (up) for more<br />

than an hour).<br />

The unit has operated for more than 1000<br />

hours without any cleaning of the<br />

condenser.<br />

Insulate better the condenser ventilation<br />

pipes and check that they slope towards<br />

the pre-arranged collection or drainage<br />

points.<br />

Check that the mains water supply is<br />

open. Check that the water drainage is<br />

correctly connected and it is not<br />

obstructed and that there are no water<br />

leaks.<br />

Check that the level float is functioning<br />

and that the collection tank loading valve<br />

is not leaking.<br />

Return micro-switch 1 to the OFF position<br />

(down)<br />

Request the intervention of the OLIMPIA<br />

SPLENDID technical service to perform<br />

the cleaning.<br />

89