17.08.2013 Views

Recycling Treated Municipal Wastewater for Industrial Water Use

Recycling Treated Municipal Wastewater for Industrial Water Use

Recycling Treated Municipal Wastewater for Industrial Water Use

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Appendix B<br />

Status of <strong>Water</strong> Reuse Regulations and Guidelines<br />

Table 5. Cali<strong>for</strong>nia Draft Ground <strong>Water</strong> Recharge Regulations<br />

Craddock Consulting Engineers B-15<br />

In Association with CDM & James Crook<br />

WWReuse Tm1_Appendix B_Regulatory.doc<br />

Contaminant Type<br />

Pathogenic Microorganisms<br />

Type of Recharge<br />

Surface spreading Subsurface injection<br />

Filtration ≤ 2 NTU<br />

Disinfection 5-log virus inactivation a , ≤ 2.2 total coli<strong>for</strong>m per 100 ml<br />

Retention time<br />

underground<br />

6 months 12 months<br />

Horizontal<br />

separation b<br />

500 ft 2000 ft<br />

Regulated Contaminants<br />

Drinking water<br />

standards<br />

Total nitrogen<br />

Unregulated Contaminants<br />

TOC e in filtered<br />

wastewater<br />

TOC in recycled<br />

water<br />

Recycled water<br />

contribution (RWC)<br />

Meet all drinking water MCLs c (except nitrogen) and new federal and state<br />

regulations as they are adopted<br />

Level specified by DHS <strong>for</strong> existing project with no RWC increase<br />

≤5 mg/L <strong>for</strong> new project or increased RWC at existing project<br />

Or NO2 d and NO3 d consistently met in mound (blending allowed)<br />

TOC ≤ 16 mg/L in any portion of the filtered wastewater not subjected to<br />

reverse osmosis (RO) treatment<br />

RO treatment as needed to achieve:<br />

TOC level specified by DHS <strong>for</strong><br />

existing project with no RWC<br />

increase<br />

TOC ≤ (0.5 mg/L)/RWC (new<br />

project or increased RWC at existing<br />

project)<br />

Compliance point is in recycled water<br />

or mound f (no blending)<br />

100% RO treatment to achieve:<br />

TOC level specified by DHS<br />

<strong>for</strong> existing project with no<br />

RWC increase<br />

TOC ≤ (0.5 mg/L)/RWC (new<br />

project or increased RWC at<br />

existing project)<br />

≤ 50 % subject to above requirements<br />

50-100 % subject to additional requirements<br />

a<br />

The virus log reduction requirement may be met by a combination of removal and inactivation.<br />

b<br />

May be reduced upon demonstration via tracer testing that the required detention time will be met at the<br />

proposed alternative distance.<br />

c<br />

MCL=maximum contaminant level.<br />

d<br />

NO2=nitrite and NO3=nitrate<br />

e<br />

TOC=total organic carbon<br />

f<br />

If mound monitoring approved.<br />

Source: Adapted from Cali<strong>for</strong>nia Department of Health Services [2004].