Section 2<br />

Implementation Considerations<br />

Table 2.4. Examples of State <strong>Water</strong> Reuse Criteria <strong>for</strong> Selected Nonpotable Applications<br />

Fodder Crop Irrigation 1<br />

Processed Food Crop Irrigation 2<br />

Food Crop Irrigation 3<br />

Restricted Recreational<br />

Impoundments 4<br />

State<br />

Treatment<br />

Quality Limits<br />

Required<br />

Treatment<br />

Quality Limits<br />

Required<br />

Treatment<br />

Quality Limits<br />

Required<br />

Treatment<br />

Quality Limits<br />

Required<br />

No detect. fecal Secondary No detect. fecal Secondary<br />

Arizona 1,000 fecal coli/100 ml Secondary Not covered Not covered coli/100 ml Filtration coli/100 ml<br />

Filtration<br />

2 NTU<br />

Disinfection 2 NTU<br />

Disinfection<br />

Cali<strong>for</strong>nia Not specified Oxidation Not specified Oxidation<br />

2.2 total coli/100<br />

ml<br />

2 NTU<br />

Oxidation<br />

Coagulation 5<br />

Filtration<br />

Disinfection<br />

2.2 total coli/100 ml<br />

Oxidation<br />

Disinfection<br />

Colorado Not covered Not covered Not covered Not covered Not covered Not covered Not covered Not covered<br />

Florida<br />

200 fecal coli/100 ml<br />

20 mg/L CBOD 6<br />

20 mg/l TSS 7<br />

Secondary<br />

Disinfection<br />

No detect. fecal<br />

coli/100 ml<br />

20 mg/L CBOD<br />

5 mg/L TSS<br />

Secondary<br />

Filtration<br />

Disinfection<br />

<strong>Use</strong> prohibited <strong>Use</strong> prohibited<br />

No detect. fecal<br />

coli/100 ml<br />

20 mg/L CBOD<br />

5 mg/L TSS<br />

Secondary<br />

Filtration<br />

Disinfection<br />

New Mexico<br />

(Policy)<br />

1,000 fecal coli/100 ml<br />

75 mg/L TSS<br />

30 mg/L BOD<br />

Not specified Not covered Not covered <strong>Use</strong> Prohibited <strong>Use</strong> Prohibited<br />

100 fecal coli/100 ml<br />

30 mg/L BOD<br />

30 mg/L TSS<br />

Not specified<br />

Utah<br />

200 fecal coli/100 ml<br />

25 mg/L BOD<br />

25 mg/L TSS<br />

Secondary<br />

Disinfection<br />

No detect. fecal<br />

coli/100 ml<br />

10 mg/L BOD<br />

2 NTU<br />

Secondary<br />

Filtration<br />

Disinfection<br />

No detect. fecal<br />

coli/100 ml<br />

10 mg/L BOD<br />

2 NTU<br />

Secondary<br />

Filtration<br />

Disinfection<br />

200 fecal coli/100 ml<br />

25 mg/L BOD<br />

25 mg/L TSS<br />

Secondary<br />

Disinfection<br />

Texas<br />

200 fecal coli/100 ml<br />

20 mg/L BOD<br />

15 mg/L CBOD<br />

Not specified<br />

200 fecal coli/100 ml<br />

20 mg/L BOD<br />

15 mg/L CBOD<br />

Not specified <strong>Use</strong> prohibited <strong>Use</strong> prohibited<br />

20 fecal coli/100 ml<br />

3 NTU<br />

5 mg/L BOD or<br />

CBOD<br />

Not specified<br />

Washington 240 total coli/100 ml<br />

Oxidation<br />

Disinfection<br />

240 total coli/100 ml<br />

Oxidation<br />

Disinfection<br />

2.2 total coli/100<br />

ml<br />

2 NTU<br />

Oxidation<br />

Coagulation<br />

Filtration<br />

Disinfection<br />

Oxidation<br />

2.2 total coli/100 ml<br />

Disinfection<br />

1<br />

In some states more restrictive requirements apply where milking animals are allowed to graze on pasture irrigated with reclaimed water.<br />

2<br />

Physical or chemical processing sufficient to destroy pathogenic microorganisms. Less restrictive requirements may apply where there is no direct contact between reclaimed<br />

water and the edible portion of the crop.<br />

3<br />

Food crops eaten raw where there is direct contact between reclaimed water and the edible portion of the crop.<br />

4<br />

Recreation is limited to fishing, boating, and other nonbody contact activities.<br />

5<br />

Not needed if filter effluent turbidity does not exceed 2 NTU, the turbidity of the influent to the filters is continually measured, the influent turbidity does not exceed 5 NTU <strong>for</strong><br />

more than 15 minutes and never exceeds 10 NTU, and there is capability to automatically activate chemical addition or divert the wastewater should the filter influent turbidity<br />

exceed 5 NTU <strong>for</strong> more than 15 minutes.<br />

6<br />

CBOD – Carbonaceous biochemical oxygen demand; where BOD is the same as Total BOD<br />

7 TSS – total suspended solids<br />

2-8 Craddock Consulting Engineers<br />

In Association with CDM & James Crook<br />