Wiring the System<br />
NOTE: The power requirements for the user-supplied power supply will<br />
vary depending on the configuration of the PLC Server and connected<br />
devices.<br />
24 VDC Power Cabling<br />
In order to maintain <s<strong>tr</strong>ong>com</s<strong>tr</strong>ong>pliance with EN standards, DC power must be delivered over a<br />
shielded cable, with the shield connected to the return conductors at both ends of the<br />
cable as shown in Figure 4-8. Conductors should be 1.5 mm 2 - 1.85 mm 2 (16 to 14 AWG) in<br />
size. The maximum length for the 24 VDC cable is 10 meters.<br />
<s<strong>tr</strong>ong>Adept</s<strong>tr</strong>ong> PLC Server<br />
- +<br />
Note: Use connector<br />
supplied by <s<strong>tr</strong>ong>Adept</s<strong>tr</strong>ong> at<br />
this end of cable.<br />
Shield<br />
User-Supplied Shielded<br />
Power Cable<br />
Figure 4-8. User Supplied Power Cable<br />
+<br />
-<br />
User-Supplied<br />
Power Supply<br />
24VDC, 5A<br />
Daisy-Chaining Power<br />
The PLC Server is equipped with two DC power connectors. These connectors allow the<br />
daisy-chaining of power from one PLC server to another. When daisy-chaining power, the<br />
power supply circuit must be limited to the lesser of 8 Amps or the amperage rating of the<br />
cabling. This can be done with a circuit breaker or a fuse. The DC power can be applied to<br />
either the XDC1 or XDC2 connector.<br />
CAUTION: Use only one 24 VDC power supply per circuit.<br />
Failure to do this could result in damage to the equipment.<br />
Installing 24 VDC Connectors<br />
Use the <s<strong>tr</strong>ong>Adept</s<strong>tr</strong>ong>-supplied connectors to connect the customer-supplied 24 VDC power<br />
supply to the PLC Server. The connectors are Weidmuller #169042.<br />
1. Locate two 24 VDC connectors that are shipped with the PLC Server. See<br />
Figure 4-9 on page 57.<br />
2. Use 14 or 16 gauge wires to connect the 24 VDC power supply to the PLC Server.<br />
3. S<strong>tr</strong>ip 7 mm of insulation from the end of the wire that connects to the positive<br />
output of the 24 VDC supply.<br />
56 <s<strong>tr</strong>ong>Adept</s<strong>tr</strong>ong> <s<strong>tr</strong>ong>Cobra</s<strong>tr</strong>ong> <s<strong>tr</strong>ong>PLC600</s<strong>tr</strong>ong>/PLC800 Robot User’s <s<strong>tr</strong>ong>Guide</s<strong>tr</strong>ong>, Rev B