CHAPTER 4: INTERFACES<br />

As indicated by the window, the Quick Connect feature quickly connects the EnerVista <strong>469</strong><br />

Setup software to a <strong>469</strong> front port with the following settings: 9600 baud, no parity, 8 bits,<br />

1 stop bit. Select the PC communications port connected to the relay and press the<br />

Connect button.<br />

The EnerVista <strong>469</strong> Setup software will display a window indicating the status of<br />

communications with the relay. When connected, a new Site called “Quick Connect” will<br />

appear in the Site List window. The properties of this new site cannot be changed.<br />

The <strong>469</strong> Site Device has now been configured via the Quick Connect feature for serial<br />

communications. Proceed to Connecting to the <strong>Relay</strong> on page 4–19 to begin<br />

communications.<br />

4.3.3 Configuring Ethernet Communications<br />

Before starting, verify that the Ethernet cable is properly connected to the RJ-45 Ethernet<br />

port.<br />

Install and start the latest version of the EnerVista <strong>469</strong> Setup<br />

software (available from the <strong>GE</strong> enerVista CD). See the previous<br />

section for the installation procedure.<br />

Click on the Device Setup button to open the Device Setup window<br />

and click the Add Site button to define a new site.<br />

Enter the desired site name in the Site Name field. If desired, a short<br />

description of site can also be entered along with the display order of<br />

devices defined for the site. In this example, we will use “Pumping<br />

Station 2” as the site name. Click the OK button when complete.<br />

The new site will appear in the upper-left list.<br />

Click the Add Device button to define the new device.<br />

Enter the desired name in the Device Name field and a description<br />

(optional).<br />

4–18 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL