CHAPTER 7: TESTING<br />

ANALOG<br />

OUTPUT<br />

FORCE<br />

VALUE<br />

EXPECTE<br />

D<br />

AMMETE<br />

R<br />

READING<br />

0 to 1 mA Analog Input<br />

A2 METERING DATA ANALOG INPUTS:<br />

MEASURED<br />

AMMETER READING<br />

(mA)<br />

Alter the following settings:<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1: “0-1 mA”<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1 MINIMUM: “0”<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1 MAXIMUM: “1000” (repeat for<br />

Analog Inputs 2 to 4)<br />

Analog output values should be ±0.01 mA on the ammeter. Measured analog input<br />

values should be ±10 units.<br />

Force the analog outputs using the following settings:<br />

S13 TESTING TEST ANALOG OUTPUT FORCE ANALOG OUTPUTS FUNCTION:<br />

“Enabled”<br />

S13 TESTING TEST ANALOG OUTPUT ANALOG OUTPUT 1 FORCED VALUE: “0%”<br />

(enter desired percent, repeats for analog output 2-4)<br />

Verify the ammeter readings as well as the measured analog input<br />

readings.<br />

View the measured values in:<br />

EXPECTED<br />

ANALOG<br />

INPUT<br />

READING<br />

A2 METERING DATA ANALOG INPUTS:<br />

MEASURED ANALOG<br />

INPUT READING<br />

(units)<br />

1 2 3 4 1 2 3 4<br />

0% 4 mA 0 mA<br />

25% 8 mA 250 mA<br />

50% 12 mA 500 mA<br />

75% 16 mA 750 mA<br />

100% 20 mA 1000 mA<br />

ANALOG<br />

OUTPUT<br />

FORCE<br />

VALUE<br />

EXPECT<br />

ED<br />

AMMETE<br />

R<br />

READIN<br />

G<br />

MEASURED<br />

AMMETER<br />

READING (mA)<br />

EXPECTED<br />

ANALOG<br />

INPUT<br />

READING<br />

MEASURED ANALOG<br />

INPUT READING<br />

(units)<br />

1 2 3 4 1 2 3 4<br />

0% 0 mA 0 mA<br />

25% 0.25 mA 250 mA<br />

50% 0.50 mA 500 mA<br />

75% 0.75 mA 750 mA<br />

100% 1.00 mA 1000 mA<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 7–9