CHAPTER 5: SETTINGS<br />

There are four (4) user-assignable digital inputs configurable to a number of different<br />

functions (see below), or turned Off. Once a function is chosen, any messages that follow<br />

may be used to set pertinent parameters for operation. Each function may only be chosen<br />

once. Assignable Inputs 1 to 4 are activated by shorting D19 to D22 (respectively) with D23.<br />

The range for the INPUT 1(4) FUNCTION settings is: Off, Remote Alarm, Remote Trip, Speed<br />

Switch Trip, Load Shed Trip, Pressure Sw Alarm, Pressure Switch Trip, Vibration Sw Alarm,<br />

Vibration Sw Trip, <strong>Digital</strong> Counter, Tachometer, General Sw A, General Sw B, General Sw C,<br />

General Sw D, Capture Trace, Simulate Pre-Fault, Simulate Fault, Simulate Pre Fault... Fault.<br />

Two-speed motor protection is enabled with the S2 SYSTEM SETUP CURRENT SENSING <br />

ENABLE 2-SPEED MOTOR PROTECTION settings. If the two-speed motor feature is enabled,<br />

Assignable Input 4 is dedicated as the two-speed motor monitor and terminals D22 and<br />

D23 are monitored for a contact closure. Closure of the contact signifies that the motor is<br />

in Speed 2 or High Speed. If the input is open, it signifies that the motor is in Speed 1. This<br />

allows the <strong>469</strong> to determine which settings should be active at any given point in time.<br />

Remote Alarm<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

These settings apply only if the INPUT 1(4) FUNCTION is “Remote Alarm”.<br />

Once the Remote Alarm function is chosen for one of the assignable digital inputs, the<br />

settings messages shown here will follow the assignment message. An alarm relay may be<br />

selected and the name of the alarm may be altered. A contact closure on the digital input<br />

assigned as Remote Alarm will cause an alarm within 100 ms with the name that has been<br />

chosen. Multiple sources may be used to trigger a remote alarm by paralleling inputs (see<br />

FIGURE 5–4: Remote Alarm/Trip from Multiple Sources on page 5–27).<br />

Remote Trip<br />

INPUT 1 FUNCTION:<br />

Remote Alarm<br />

REMOTE ALARM<br />

NAME:<br />

REMOTE<br />

ALARM: Unlatched<br />

Range: See above<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

ASSIGN ALARM<br />

RELAYS:<br />

REMOTE ALARM<br />

EVENTS: Off<br />

INPUT 1 FUNCTION:<br />

Remote Trip<br />

REMOTE TRIP NAME:<br />

Remote Trip<br />

ASSIGN TRIP<br />

RELAYS:<br />

Range: 20 alphanumeric characters<br />

Range: Latched, Unlatched<br />

Range: Alarm, Alarm & Aux2, Alarm &<br />

Aux2 & Aux3, Alarm & Aux3,<br />

Auxiliary2, None<br />

Range: On, Off<br />

Range: See above<br />

Range: 20 character alphanumeric<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

5–26 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL