06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CHAPTER 2: INTRODUCTION<br />

Note<br />

2.2.6 Power Supply<br />

2.2.7 CPU<br />

Block from start: .............................................0 to 5000 s in steps of 1<br />

Pickup accuracy: ............................................at Iavg < 2 × CT: ±1% of 3 × 2 × CT × VT × VTfull scale<br />

at Iavg > 2 × CT: ±1.5% of 3 × 20 × CT × VT × VTfull scale<br />

Timing accuracy: ...........................................±100ms or ± 0.5% of total time<br />

Elements:............................................................Trip and Alarm<br />

THREE-PHASE REAL POWER<br />

Range:..................................................................0 to ±99999 kW<br />

Pickup: .................................................................1 to 25000 kW in steps of 1<br />

Time delay:........................................................1 to 30 s in steps of 1<br />

Block from start: ............................................0 to 15000 s in steps of 1<br />

Pickup Accuracy: ............................................at Iavg < 2 × CT:±1% of 3 × 2 × CT × VT × VTfull scale<br />

at Iavg > 2 × CT±1.5% of 3<br />

× 20 × CT × VT × VTfull scale<br />

Timing accuracy: ...........................................±0.5 s or ±0.5% of total time<br />

CONTROL POWER<br />

Options:...............................................................LO / HI (must be specified with order)<br />

LO range:............................................................20 to 60 V DC<br />

20 to 48 V AC at 48 to 62 Hz<br />

HI range:.............................................................90 to 300 V DC<br />

70 to 265 V AC at 48 to 62 Hz<br />

Power:..................................................................45 VA (max), 25 VA typical<br />

Total loss of voltage ride through time<br />

(0% control power): 16.7 ms<br />

FUSE (HI and LO VOLT)<br />

Current rating: ................................................2.50 A<br />

Type: .....................................................................5 × 20 mm SLO-BLO HRC Littelfuse, high breaking<br />

capacity<br />

Model no.:...........................................................215-02.5<br />

An external fuse must be used if the supply voltage exceeds 250 V.<br />

COMMUNICATIONS<br />

RS232 port:........................................................1, front panel, non-isolated<br />

RS485 ports:......................................................2, isolated together at 36 V pk<br />

Baud rates:........................................................300, 1200, 2400, 4800, 9600, and 19200 (for RS485);<br />

9600 (for RS232)<br />

Parity:...................................................................None, Odd, Even<br />

Ethernet: .............................................................10Base-T RJ45 connector<br />

Modbus TCP/IP<br />

Version 2.0 / IEEE 802.3<br />

MODBUS<br />

Modbus: ..............................................................Modbus ® RTU / half-duplex<br />

DEVICENET<br />

Baud rate: ..........................................................125K, 250K, 500K<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 2–13