Table 5–3: Analog Output Parameter Selection Table<br />

CHAPTER 5: SETTINGS<br />

PARAMETER NAME RAN<strong>GE</strong> / UNITS STEP DEFAULT<br />

MIN. MAX<br />

Phase A Current 0 to 100000 A 1 0 100<br />

Phase B Current 0 to 100000 A 1 0 100<br />

Phase C Current 0 to 100000 A 1 0 100<br />

Avg. Phase Current 0 to 100000 A 1 0 100<br />

AB Line Voltage 50 to 20000 V 1 3200 4500<br />

BC Line Voltage 50 to 20000 V 1 3200 4500<br />

CA Line Voltage 50 to 20000 V 1 3200 4500<br />

Avg. Line Voltage 50 to 20000 V 1 3200 4500<br />

Phase AN Voltage 50 to 20000 V 1 1900 2500<br />

Phase BN Voltage 50 to 20000 V 1 1900 2500<br />

Phase CN Voltage 50 to 20000 V 1 1900 2500<br />

Avg. Phase Voltage 50 to 20000 V 1 1900 2500<br />

Hottest Stator RTD –50 to +250°C or –58 to +482°F 1 0 200<br />

Hottest Bearing RTD –50 to +250°C or –58 to +482°F 1 0 200<br />

Ambient RTD –50 to +250°C or –58 to +482°F 1 -50 60<br />

RTD #1 to 12 –50 to +250°C or –58 to +482°F 1 -50 250<br />

Power Factor 0.01 to 1.00 lead/lag 0.01 0.8 lag 0.8 lead<br />

Reactive Power -50000 to 50000 kvar 1 0 750<br />

Real Power -50000 to 50000 kW 1 0 1000<br />

Apparent Power 0 to 50000 kVA 1 0 1250<br />

Thermal Capacity Used 0 to 100% 1 0 100<br />

<strong>Relay</strong> Lockout Time 0 to 500 min. 1 0 150<br />

Current Demand 0 to 100000 A 1 0 700<br />

kvar Demand 0 to 50000 kvar 1 0 1000<br />

kW Demand 0 to 50000 kW 1 0 1250<br />

kVA Demand 0 to 50000 kVA 1 0 1500<br />

<strong>Motor</strong> Load 0.00 to 20.00 x FLA 0.01 0.00 1.25<br />

Analog Inputs 1-4 –50000 to +50000 1 0 +50000<br />

Tachometer 100 to 7200 RPM 1 3500 3700<br />

5–92 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL