5.11.3 Reactive Power<br />

PATH: SETTINGS S10 POWER ELEMENTS REACTIVE POWER<br />

<br />

REACTIVE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

BLOCK kvar ELE-<br />

MENT<br />

REACTIVE POWER<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

POSITIVE kvar<br />

ALARM<br />

NEGATIVE kvar<br />

ALARM<br />

REACTIVE POWER<br />

ALARM<br />

REACTIVE POWER<br />

ALARM<br />

REACTIVE POWER<br />

TRIP: Off<br />

ASSIGN TRIP<br />

RELAYS:<br />

POSITIVE kvar<br />

TRIP<br />

NEGATIVE kvar<br />

TRIP<br />

REACTIVE POWER<br />

TRIP<br />

CHAPTER 5: SETTINGS<br />

Range: 0 to 5000 s in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 1 to 25000 kvar in steps of 1<br />

Range: 1 to 25000 kvar in steps of 1<br />

Range: 0.2 to 30.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 1 to 25000 kvar in steps of 1<br />

Range: 1 to 25000 kvar in steps of 1<br />

Range: 0.2 to 30.0 s in steps of 0.1<br />

If the <strong>469</strong> is applied on a synchronous motor, it is desirable not to trip or alarm on kvar until<br />

the field has been applied. Therefore, this feature can be blocked until the motor comes up<br />

to speed and the field is applied. From that point forward, the kvar trip and alarm elements<br />

will be active. Once the kvar level exceeds either the positive or negative level, for the<br />

specified delay, a trip or alarm will occur indicating a positive or negative kvar condition.<br />

The reactive power alarm can be used to detect loss of excitation and out of step.<br />

5–82 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL