CHAPTER 6: ACTUAL VALUES<br />

6.2.2 <strong>Motor</strong> Status<br />

PATH: ACTUAL VALUES A1 STATUS MOTOR STATUS<br />

MOTOR<br />

STATUS []<br />

6.2.3 Last Trip Data<br />

These messages describe the motor status at any given point in time. If the motor has<br />

been tripped and the <strong>469</strong> has not yet been reset, the MOTOR STATUS value will be “Tripped”.<br />

The MOTOR THERMAL CAPACITY USED reflects an integrated value of both the Stator and<br />

Rotor Thermal Capacity Used. The values for ESTIMATED TRIP TIME ON OVERLOAD appear<br />

whenever the <strong>469</strong> picks up on the overload curve.<br />

PATH: ACTUAL VALUES A1 STATUS LAST TRIP DATA<br />

LAST<br />

TRIP []<br />

DATA<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MOTOR STATUS:<br />

Stopped<br />

MOTOR THERMAL<br />

CAPACITY USED: 0%<br />

ESTIMATED TRIP<br />

TIME<br />

MOTOR SPEED:<br />

Low Speed<br />

CAUSE OF LAST<br />

TRIP:<br />

No Trip to Date<br />

TIME OF LAST<br />

TRIP:<br />

DATE OF LAST<br />

TRIP:<br />

MOTOR SPEED DUR-<br />

ING<br />

TACHOMETER<br />

PreTrip: 3600 RPM<br />

A: 0 B:<br />

0<br />

MOTOR LOAD:<br />

0.00 x FLA Pre-<br />

CURRENT UNBALANCE<br />

PreTrip: 0%<br />

GROUND CURRENT<br />

PreTrip: 0.00<br />

A: 0 B: 0<br />

C: 0 A<br />

HOTTEST STATOR<br />

RTD<br />

Range: Tripped, Stopped, Starting,<br />

Running, Overload<br />

Range: 0 to 100%<br />

Range: 0 to 10000 sec., Never<br />

Range: HIgh Speed, Low Speed. Seen if<br />

two speed motor is enabled<br />

Range: see below<br />

Range: hour:min:sec<br />

Range: Month Day Year<br />

Range: High Speed, Low Speed. Seen if<br />

two-speed motor is enabled<br />

Range: 0 to 3600 RPM. Seen if a <strong>Digital</strong><br />

Input set as Tachometer.<br />

Range: 0 to 100000 A<br />

Range: 0.00 to 20.00 x FLA<br />

Range: 0 to 100%<br />

Range: 0.0 to 5000.0 A. Not seen if<br />

Ground CT is set to “None”.<br />

Range: 0 to 5000 A. Not seen if<br />

Differential CT is set as None<br />

Range: –50 to 250°C or –58 to 482°F.<br />

Seen only if at least 1 RTD is set<br />

as Stator<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 6–5