Pressure Switch Alarm<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

These settings apply only if the INPUT 1(4) FUNCTION is “Pressure Sw. Alarm”.<br />

CHAPTER 5: SETTINGS<br />

Once the pressure switch alarm function is chosen for one of the assignable digital inputs,<br />

the settings messages shown here will follow the assignment message. The Pressure<br />

Switch alarm feature may be blocked for a specified period of time from a motor start. A<br />

value of zero for the block time indicates that the feature is always active, when the motor<br />

is stopped or running. After the block delay has expired, the digital input will be monitored.<br />

If a closure occurs, after the specified delay, an alarm will occur.<br />

Pressure Switch Trip<br />

INPUT 1 FUNCTION:<br />

Pressure Sw Alarm<br />

BLOCK PRES. SW.<br />

ALARM<br />

PRESSURE SWITCH<br />

ALARM: Unlatched<br />

Range: See above<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

ASSIGN ALARM<br />

RELAYS:<br />

PRESSURE SW.<br />

ALARM<br />

PRESSURE SW.<br />

ALARM<br />

INPUT 1 FUNCTION:<br />

Pressure Switch<br />

BLOCK PRES. SW.<br />

TRIP<br />

ASSIGN TRIP<br />

RELAYS:<br />

PRESSURE SW. TRIP<br />

DELAY: 5.0 s<br />

Range: 0 to 5000 s in steps of 1<br />

Range: Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Auxiliary2 & Aux3,<br />

Alarm & Auxiliary3, Auxiliary2,<br />

Aux2 & Aux3, Auxiliary3, None<br />

Range: 0.1 to 100.0 sec., step: 0.1<br />

Range: On, Off<br />

Range: See above<br />

Range: 0 to 5000 sec.; step: 1<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 0.1 to 100.0 s in steps of 0.1<br />

These settings apply only if the INPUT 1(4) FUNCTION is “Pressure Switch Trip”.<br />

Once the Pressure Switch Trip function is chosen for one of the digital inputs, the settings<br />

messages shown here will follow the assignment message. The Pressure Switch Trip<br />

feature may be blocked for a specified period of time from a motor start. A value of zero for<br />

the Block time indicates that the feature is always active, when the motor is stopped or<br />

running. After the block delay has expired, the digital input will be monitored. If a closure<br />

occurs, after the specified delay, a trip will occur.<br />

5–28 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL