CHAPTER 5: SETTINGS<br />

Note<br />

5.13.3 Analog Input Diff 1-2<br />

PATH: SETTINGS S12 ANALOG I/O ANALOG INPUT DIFF 1–2<br />

ANALOG<br />

INPUT []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

ANALOG IN DIFF 1-<br />

2:<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

A/I DIFF 1-2<br />

BLOCK<br />

ANALOG IN DIFF 1-<br />

2<br />

ASSIGN ALARM<br />

RELAYS:<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

ASSIGN TRIP<br />

RELAYS:<br />

ANALOG IN DIFF 1-<br />

2<br />

ANALOG IN DIFF 1-<br />

2<br />

Range: Disabled, Enabled<br />

Range: 12 alphanumeric characters<br />

Range: % Diff, Abs. Diff<br />

Range: 12, 1>2, 2>1<br />

Range: Always, Start/Run<br />

Range: 0 to 5000 s in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 0 to 500% in steps of 1 or<br />

0 to 50000 Units in steps of 1<br />

Range: 0.1 to 300.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3 Trip & Auxiliary3<br />

Range: 0 to 500% in steps of 1 or<br />

0 to 50000 Units in steps of 1<br />

Range: 0.1 to 300.0 s in steps of 0.1<br />

This settings menu is seen only if Analog Inputs 1 and 2 are enabled. The ANALOG IN DIFF 1-<br />

2 TRIP LEVEL and ANALOG IN DIFF 1-2 ALARM LEVEL settings are shown units of “%” if the<br />

ANALOG IN DIFF 1-2 COMPARISON is “%Diff” or in units defined by the ANALOG INPUT 1 UNITS<br />

settings if ANALOG IN DIFF 1-2 COMPARISON is “Abs Diff”.<br />

This feature compares two analog inputs and activate alarms or trips based on their<br />

difference, which can be an absolute difference in units or a percentage difference. The<br />

second analog input (2 for 1-2) is used as the reference value for percentage calculations.<br />

The comparison logic can also be selected as one input greater than the other (“1>2”) or<br />

vice versa (“2>1”) or as absolute difference (“12”). The compared analog inputs must be<br />

programmed with the same units type prior to programming this feature.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–95