5.14 S13 <strong>469</strong> Testing<br />

5.14.1 Simulation Mode<br />

PATH: SETTINGS S13 <strong>469</strong> TESTING SIMULATION MODE<br />

<br />

SIMULATION [<br />

MESSA<strong>GE</strong><br />

SIMULATION MODE:<br />

Off<br />

PRE-FAULT TO<br />

FAULT<br />

CHAPTER 5: SETTINGS<br />

Range: Off, Simulate Pre-Fault,<br />

Simulate Fault, Pre-Fault to<br />

Fault<br />

Range: 0 to 300 s in steps of 1<br />

The <strong>469</strong> may be placed in several simulation modes. This simulation may be useful for<br />

several purposes.<br />

• First, it may be used to understand the operation of the <strong>469</strong> for learning or training<br />

purposes.<br />

• Second, simulation may be used during startup to verify that control circuitry<br />

operates as it should in the event of a trip, alarm, or block start.<br />

• In addition, simulation may be used to verify that settings had been set properly in<br />

the event of fault conditions.<br />

Simulation mode may be entered only if the motor is stopped and there are no trips,<br />

alarms, or block starts active. The values entered as Pre-Fault Values will be substituted for<br />

the measured values in the <strong>469</strong> when the simulation mode is “Simulate Pre-Fault”. The<br />

values entered as Fault Values will be substituted for the measured values in the <strong>469</strong> when<br />

the simulation mode is “Simulate Fault”. If the simulation mode: Pre-Fault to Fault is<br />

selected, the Pre-Fault values will be substituted for the period of time specified by the<br />

delay, followed by the Fault values. If a trip occurs, simulation mode will revert to Off.<br />

Selecting “Off” for the simulation mode will place the <strong>469</strong> back in service. If the <strong>469</strong><br />

measures phase current or control power is cycled, simulation mode will automatically<br />

revert to Off.<br />

If the <strong>469</strong> is to be used for training, it might be desirable to allow all learned parameters,<br />

statistical information, and event recording to update when operating in simulation mode.<br />

If however, the <strong>469</strong> has been installed and will remain installed on a specific motor, it might<br />

be desirable to short the <strong>469</strong> Test input (C3 and C4) to prevent all of this data from being<br />

corrupted or updated. In any case, when in simulation mode, the <strong>469</strong> In Service LED<br />

(indicator) will flash, indicating that the <strong>469</strong> is not in protection mode.<br />

5–98 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL