CHAPTER 5: SETTINGS<br />

5.15 S14 Two-Speed <strong>Motor</strong><br />

5.15.1 Description<br />

The two-speed motor feature provides proper protection for a two-speed motor where<br />

there will be two different full load values. The algorithm integrates the heating at each<br />

speed into one thermal model using a common thermal capacity used register value for<br />

both speeds.<br />

If the two-speed motor feature is used, Assignable Input 4 is dedicated as the two-speed<br />

motor monitor and terminals D22 and D23 are monitored for a contact closure. Contact<br />

closure signifies that the motor is in Speed 2; if the input is open, it signifies that the motor<br />

is in Speed 1. This allows the <strong>469</strong> to determine which settings should be active at any given<br />

point in time. Two-speed motor protection is enabled with the S2 SYSTEM SETUP CURRENT<br />

SENSING ENABLE 2-SPEED MOTOR PROTECTION settings.<br />

Speed2 Overload Setup<br />

• Overview<br />

The settings corresponding to the Speed2 Overload Curve are closely related to the<br />

Thermal Model curve style and overload curve settings. Refer to 5.6.2 Thermal Model on<br />

page 5–38 and 5.6.3 Overload Curve Setup on page 5–39 for details. When setting the<br />

Speed2 Overload Curve characteristics, only the relevant settings corresponding to the<br />

overload curve style will be shown, as described below.<br />

• Standard Overload Curves<br />

If the SELECT CURVE STYLE is set to “Standard” in the Thermal Model, the following settings<br />

will appear:<br />

PATH: SETTINGS S14 2-SPEED MOTOR SPEED2 OVERLOAD SETUP<br />

<br />

SPEED2 [<br />

Refer to Standard Overload Curves on page 5–39 for additional details on the standard<br />

overload curves available for Speed2.<br />

• Custom Overload Curves<br />

If the SELECT CURVE STYLE is set to “Custom” in the Thermal Model, the following settings<br />

will appear:<br />

PATH: SETTINGS S14 2-SPEED MOTOR SPEED2 OVERLOAD SETUP<br />

<br />

SPEED2 [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

SPEED2 STANDARD<br />

CURVE NUMBER: 4<br />

SPEED2 TRIP AT<br />

1.01 x FLA:<br />

SPEED2 TRIP AT<br />

1.05 x FLA:<br />

SPEED2 TRIP AT<br />

1.10 x FLA:<br />

SPEED2 TRIP AT<br />

1.20 x FLA: 795.4<br />

Range: 1 to 15 in steps of 1<br />

Range: 0.5 to 99999.9 in steps of 0.1<br />

Range: 0.5 to 99999.9 in steps of 0.1<br />

Range: 0.5 to 99999.9 in steps of 0.1<br />

Range: 0.5 to 99999.9 in steps of 0.1<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–103