CHAPTER 5: SETTINGS<br />

5.3.5 Reduced Voltage<br />

PATH: SETTINGS S2 SYSTEM SETUP REDUCED VOLTA<strong>GE</strong> STARTING<br />

<br />

REDUCED [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

REDUCED VOLTA<strong>GE</strong><br />

STARTING: Off<br />

ASSIGN CONTROL<br />

RELAYS:<br />

TRANSITION ON:<br />

Current Only<br />

ASSIGN TRIP<br />

RELAYS:<br />

REDUCED VOLTA<strong>GE</strong><br />

START LEVEL: 100%<br />

REDUCED VOLTA<strong>GE</strong><br />

START TIMER: 200<br />

Range: On, Off<br />

Range: Auxilary2, Aux2 & Aux3,<br />

Auxiliary3<br />

Range: Current Only, Current or Timer,<br />

Current and Timer<br />

Range: Trip, Trip & Aux2, Trip & Aux2 &<br />

Aux3, Trip & Aux3<br />

Range: 25 to 300% in steps of 1<br />

Range: 1 to 600 s in steps of 1<br />

The <strong>469</strong> can control the transition of a reduced voltage starter from reduced to full voltage.<br />

That transition may be based on “Current Only”, “Current and Timer”, or “Current or Timer”<br />

(whichever comes first). When the <strong>469</strong> measures the transition of no motor current to<br />

some value of motor current, a 'Start' is assumed to be occurring (typically current will rise<br />

quickly to a value in excess of FLA, e.g. 3 × FLA). At this point, the REDUCED VOLTA<strong>GE</strong> START<br />

TIMER is initialized with the programmed value in seconds.<br />

• If “Current Only” is selected, when the motor current falls below the user's<br />

programmed Transition Level, transition will be initiated by activating the assigned<br />

output relay for 1 second. If the timer expires before that transition is initiated, an<br />

Incomplete Sequence Trip will occur activating the assigned trip relay(s).<br />

• If “Current or Timer” is selected, when the motor current falls below the user's<br />

programmed Transition Level, transition will be initiated by activating the assigned<br />

output relay for 1 second. If the timer expires before that transition is initiated, the<br />

transition will be initiated regardless.<br />

• If “Current and Timer” is selected, when the motor current falls below the user's<br />

programmed Transition Level and the timer expires, transition will be initiated by<br />

activating the assigned output relay for 1 second. If the timer expires before current<br />

falls below the Transition Level, an Incomplete Sequence Trip will occur activating the<br />

assigned trip relay(s).<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–21