5.9.5 RTD 12<br />

CHAPTER 5: SETTINGS<br />

RTD. Trip voting has been added for extra reliability in the event of RTD malfunction. If<br />

enabled, a second RTD must also exceed the trip temperature of the RTD being checked<br />

before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is<br />

disabled. The RTD name may be changed if desired.<br />

PATH: SETTINGS S8 RTD TEMPERATURE RTD 12<br />

RTD<br />

#12 []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

RTD #12 APPLICA-<br />

TION:<br />

RTD #12 NAME:<br />

RTD #12 ALARM:<br />

Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

RTD #12 ALARM<br />

TEMPERATURE: 60°C<br />

RTD #12 HIGH<br />

ALARM:<br />

HIGH ALARM<br />

RELAYS:<br />

RTD #12 HIGH<br />

ALARM<br />

RTD #12 ALARM<br />

EVENTS: Off<br />

RTD #12 TRIP:<br />

Off<br />

RTD #12 TRIP VOT-<br />

ING:<br />

ASSIGN TRIP<br />

RELAYS:<br />

RTD #12 TRIP<br />

TEMPERATURE: 80°C<br />

Range: Stator, Bearing, Ambient, Other,<br />

None<br />

Range: 8 alphanumeric characters<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 1 to 250°C in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 1 to 250°C in steps of 1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: RTD #1 to RTD #12<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 1 to 250°C in steps of 1<br />

RTDs 12 defaults to “Ambient” RTD type. There are individual alarm, high alarm and trip<br />

configurations for this RTD. Trip voting has been added for extra reliability in the event of<br />

RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the<br />

RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself, the<br />

voting feature is disabled. The RTD name may be changed if desired.<br />

5–74 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL