6.2 A1 Status<br />

6.2.1 Network Status<br />

Ethernet Connection<br />

PATH: ACTUAL VALUES A1 STATUS NETWORK STATUS<br />

NETWORK<br />

STATUS []<br />

Ethernet Lnk Con<br />

Dia<br />

CHAPTER 6: ACTUAL VALUES<br />

This actual value appears when the relay is ordered with the Ethernet (T) option.<br />

The ETHERNET STATUS actual value message indicates the status of the Ethernet link,<br />

connection, and diagnostic via three indicators. The [] symbol indicates on, and the [ ]<br />

symbol indicates off. There is also a blinking indication.<br />

The box under LNK column indicates the Ethernet link status. If it is on, the Ethernet port is<br />

connected to the network; if it is off, the port is disconnected. This indicator is normally on.<br />

The box under the CON column indicates the connection status. If on, the Ethernet port is<br />

configured and ready to transmit and receive data. If blinking, the Ethernet port is either<br />

active (transmitting or receiving data) or indicating an error if the diagnostic status is also<br />

on or blinking.<br />

The box under the DIA column indicates the diagnostic status. If it is on, then either a fatal<br />

Ethernet port error has occurred or there is a duplicate IP address on the network. If<br />

blinking, then there is a non-fatal network error. Off indicates no errors.<br />

DeviceNet Connection (Refer to <strong>GE</strong>K-106491C: <strong>469</strong> Communications Guide)<br />

PATH: ACTUAL VALUES A1 STATUS NETWORK STATUS<br />

NETWORK<br />

STATUS []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

DEVICENET PORT:<br />

Not powered<br />

DEVICENET LINK:<br />

Not online<br />

EXPLICIT CONNEC-<br />

TION:<br />

POLLED I/O<br />

CONNECTN: Nonex-<br />

COS CONNECTION<br />

STATUS: Nonexis-<br />

Range: see description below<br />

Range: Not powered, operational, Data<br />

size error, Unrecoverable fault,<br />

Minor fault<br />

Range: Not online, Online connected,<br />

Online disconnected, Critical<br />

failure, Connection timeout<br />

Range: Nonexistent, Configuring,<br />

Established, Time-out,<br />

Deferred Delete<br />

Range: Nonexistent, Configuring,<br />

Established, Time-out,<br />

Deferred Delete<br />

Range: Nonexistent, Configuring,<br />

Established, Time-out,<br />

Deferred Delete<br />

These values appear when the relay is ordered with the DeviceNet (D) option.<br />

6–4 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL