7.2.7 Analog Inputs and Outputs<br />

A1 STATUS DIGITAL INPUTS<br />

INPUT EXPECTED<br />

STATUS (SWITCH<br />

OPEN)<br />

CHAPTER 7: TESTING<br />

The <strong>469</strong> specification for analog input and analog output accuracy is ±1% of full scale.<br />

Perform the steps below to verify accuracy. Verify the Analog Input +24 V DC with a<br />

voltmeter.<br />

4 to 20 mA Analog Input<br />

Alter the following settings:<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1: “4-20 mA”<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1 MINIMUM: “0”<br />

S12 ANALOG I/O ANALOG INPUT1 ANALOG INPUT1 MAXIMUM: “1000” (repeat this<br />

value for Analog Inputs 2 to 4)<br />

Analog output values should be ±0.2 mA on the ammeter. Measured analog input<br />

values should be ±10 units.<br />

Force the analog outputs using the following settings:<br />

S13 TESTING TEST ANALOG OUTPUT FORCE ANALOG OUTPUTS FUNCTION:<br />

“Enabled”<br />

S13 TESTING TEST ANALOG OUTPUT ANALOG OUTPUT 1 FORCED VALUE: “0%”<br />

(enter desired value in percent; repeat for Analog Outputs 2 through 4)<br />

Verify the ammeter readings as well as the measured analog input<br />

readings.<br />

For the purposes of testing, the analog input is fed in from the analog<br />

output (see FIGURE 7–1: Secondary Injection Test Setup on page 7–2).<br />

View the measured values in:<br />

PASS /<br />

FAIL<br />

ACCESS Open Shorted<br />

TEST Open Shorted<br />

STARTER STATUS Open Shorted<br />

EMER<strong>GE</strong>NCY RESTART Open Shorted<br />

REMOTE RESET Open Shorted<br />

ASSIGNABLE INPUT 1 Open Shorted<br />

ASSIGNABLE INPUT 2 Open Shorted<br />

ASSIGNABLE INPUT 3 Open Shorted<br />

ASSIGNABLE INPUT 4 Open Shorted<br />

TRIP COIL SUPERVISION No Coil Coil<br />

EXPECTED<br />

STATUS (SWITCH<br />

CLOSED)<br />

PASS /<br />

FAIL<br />

7–8 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL